Chapter 5 Functional Parameter Simple List 200 Series General Purpose Vector AC Drive
40
F3-04 Motor resistance of rotor
0.001
Ω
~
32.000
Ω
(ac drive power<=55kW)
0.0001
Ω
~
3.2000
Ω
(ac drive power>55kW)
Tuning
parameters
×
*
F3-05
Leakage inductance of
stator and rotor
0.01mH
~
320.00mH(ac drive power<=55kW)
0.001mH
~
32.000mH(ac drive power>55kW)
Tuning
parameters
×
*
F3-06
Motor stator and rotor
mutual inductance
0.1mH
~
3200.0mH(ac drive power<=55kW)
0.01mH
~
320.00mH(ac drive power>55kW)
Tuning
parameters
×
*
F3-07
Motor current without
load
0.01A
~
F3-01(ac drive power<=55kW)
0.1A
~
F3-01(ac drive power>55kW)
Tuning
parameters
×
*
F3-08
Motor parameter
auto-learning
0: No operation
1: Parameter dynamic auto-learning(The motor
first auto-learning statically, then auto-learning
when rotating)
2: Parameter static auto-learning (Without
motor running)
0 ×
*
F3-09
Speed loop proportional
gain 1
1
~
100
50
√
F3-10
Speed loop integral time
1
0.01
~
10.00s
1.00s
√
F3-11
The low frequency point
to switch
0.0
~
F3-14
5.00Hz
√
F3-12
Speed loop proportional
gain 2
1
~
100
30
√
F3-13
Speed loop integral time
2
0.01
~
10.00s
1.00s
√
F3-14
The high frequency point
to switch
F3-11
~
F0-05
10.00Hz
√
F3-15
Coefficient of VC Slip
compensation
50%
~
200%
100%
√
F3-16
Electric torque setting(
speed control)
50.0%
~
300.0%
200.0%
√
F3-17
Torque setting mode
selection
0: Torque digit set(F3-18)
1: Analog V1 set
2: Analog V2 set
3: Remote communication setting
4: Keyboard potentiometer setting (LCD
keyboard only)
When it sets as 1-2,the corresponding biggest
value is F3-18
0
√
F3-18
Torque digit setting
(torque control )
-200.0%
~
200.0%
100.0%
√
F3-19
Upper limit frequency
source selection
0: Upper limit frequency set by keyboard
(F0-06)
0 ×