Chapter 5 Functional Parameter Simple List 200 Series General Purpose Vector AC Drive
48
time
F6-30
PLC phase 14 operation
time
0.0
~
3200.0s
0.0s
√
F6-31
PLC phase 15 operation
time
0.0
~
3200.0s
0.0s
√
F6-32 PLC function selection
Unit: Cycle mode selection
0: Stop after operating for 1 cycle
1: Holding at the final value after single cycle
of operation
2: Cycle continuously
Ten: Breakpoint recovery selection
0: Run from phase 1
1: Continue to run from the stopping time
Hundreds : Power off with stored selection
0: No store if power off
1: Store if power off
Thousands: phase time unit
0: s
1: Min
2: H
0000 ×
F6-33
PLC target frequency set
unit
0: Percentage setting
1: Frequency HZ setting
0 ×
Group F7: Process PID Parameter Group
F7-00
PID control function
selection
The unit : PID specified channel selection
0: Keypad digital frequency setting(F7-02)
1: Analog V1 setting
2: Analog V2 setting
3: Communication settings
Ten: PID feedback channel selection
0: Analog V1 feedback
1: Analog V2 feedback
2: Communication settings
Hundred: PID output characteristic selection
0: PID output positive characteristic(The
smaller the PID feedback, the larger the
frequency output)
1: PID output negative characteristic(The
smaller the PID feedback, the smaller the
frequency output)
0000
√
F7-01
Feedback protection
function selection
Unit: Feedback disconnection detected
selection
0: Invalid
1: Arm and operation in settled frequency
0000
√