Chapter 6 Key Functional Parameter Explanation In Detail 200 Series General Purpose Vector AC Drive
60
Voltage %
Vb:F0-16
V3:F2-08
V2:F2-06
V1:F2-04
F1
:F
2-
03
F2
:F
2-
05
F3
:F
2-
07
Fb
:F
0-
17
Frequency Hz
V1-V3: Multi-segment V/F 1st~3rd stage
voltage percentage
F1-F3: Multi-segment V/F 1st~3rd stage
frequency
Vb: Motor rated voltage
Fb: Motor rated frequency
Figure 6-3 Multi-point V/F curve setting diagarm
F3-00 Motor
rated
power
Set range: 0.4kW
~
1000.0kW
Model depends
F3-01 Motor rated current
Set range: 0.1A
~
3200.0A
Model depends
F3-02 Motor rated speed
Set range: 10rpm
~
32000rpm
Model depends
F0-16 Motor
rated
voltage Set range: 10V
~
1000V
Factory default: 380V
F0-17 Motor rated frequency Set range: 0.01Hz
~
F0-05
Factory default: 50.00Hz
The above function codes are motor nameplate parameters. Regardless of whether VF control or vector
control is adopted, the relevant parameters need to be accurately set according to the motor nameplate.
F3-03
Motor resistance of
stator
0.001
Ω
~
32.000
Ω
(ac drive power<=55kW)
0.0001
Ω
~
3.2000
Ω
(ac drive power>55kW)
Tuning parameters
F3-04
Motor resistance of
rotor
0.001
Ω
~
32.000
Ω
(ac drive power<=55kW)
0.0001
Ω
~
3.2000
Ω
(ac drive power>55kW)
Tuning parameters
F3-05
Leakage inductance of
stator and rotor
0.01mH
~
320.00mH(ac drive power<=55kW)
0.001mH
~
32.000mH(ac drive power>55kW)
Tuning parameters
F3-06
Motor stator and rotor
mutual inductance
0.1mH
~
3200.0mH(ac drive power<=55kW)
0.01mH
~
320.00mH(ac drive power>55kW)
Tuning parameters
F3-07
Current without motor
load
0.01A
~
F3-01(ac drive power<=55kW)
0.1A
~
F3-01(ac drive power>55kW)
Tuning parameters
F3-03
~
F3-07 are the parameters of asynchronous motors. These parameters are generally not on the
motor nameplate and need to be automatically tuned by the ac drive. Among them, "Asynchronous motor
static parameter auto-learning" can only obtain three parameters from F3-03 to F3-05, and "Asynchronous
motor dynamic parameter auto-learning" can obtain all 5 parameters here.
When changing the rated power of the motor (F3-00), the ac drive will automatically modify the
parameter values of F3-01
~
F3-07, and restore these 5 parameters to the commonly standard Y series
motor parameters.
If it is not possible to tune the asynchronous motor on site, the corresponding function code above can
be entered according to the parameters provided by the motor manufacturer.
F3-08 Motor
parameter
auto-learning Set range: 0
~
2
Factory default::0