200 Series General Purpose Vector AC Drive Chapter 3 Mechanical and Electrical Installation
25
Chapter 3 Mechanical and Electrical Installation
3.1 External Electrical Components Selection Guide
Power
(KW)
Air Switch
(MCCB)
Recommended
Contactor
(A)
Recommended
Input Side Main
Circuit Guide
Line(mm
2
)
Recommended
Output Side Main
Circuit Guide Line
(mm
2
)
Recommended
Control Circuit
Guide Line (mm
2
)
0.4 6 9 0.75 0.75
0.5
0.75 6 9
0.75
0.75
0.5
1.5 10 9
0.75
0.75
0.5
2.2 10 9
0.75
0.75
0.5
3.0 16 12
1.5
1.5
0.5
3.7 16 12
1.5
1.5
0.5
5.5 20 18
2.5
2.5
0.75
7.5 32 25
4.0
4.0
0.75
11 40 32
4.0
4.0
0.75
15 50 38
6.0
6.0
0.75
18.5 50 40
10
10
1.0
22 63 50
10
10
1.0
30 100 65
16
16
1.0
37 100 80
25
25
1.0
45 123 95
35
35
1.0
55 160 115
50
50
1.0
75 225 170
70
70
1.0
93 250 205
95
95
1.0
110 315 245
95
95
1.0
132 350 300
120
120
1.0
160 400 300
150
150
1.0
185 500 410
150
150
1.0
200 500 410
185
185
1.0
220 630 475
240
240
1.0
250 630 475 2*120 2*120
1.0
280 700 620 2*120 2*120
1.0
315 800 800 2*150 2*150
1.0
350 1000 1000 2*185
2*185
1.0
400 1250 1000 2*240
2*240
1.0
450 1250 1290 2*240
2*240
1.0
500 1600 1290 4*150
4*150
1.0
550 1600 1600 4*150
4*150
1.0
630 1600 1600 4*150
4*150
1.0
700 1600 1600 4*150
4*150
1.0