Chapter 7 Communication Protocol 200 Series General Purpose Vector AC Drive
71
address could not use to read the AC Drive function parameter.
2
、
Examples of communication frame content
The dec. time of AC Drive should change to 30.0s through upper machine, corresponding 16 system data
is 012CH, and store this setting when power-off. Dec time F0-11 responds the address of 16 system is
F00BH.
And the upper machine sends the data to AC Drive as follows
Slave
address
Function
code
Parameter
address high byte
Parameter
address low byte
Data
high byte
Data low
byte
CRC Parity
bit high byte
CRC Parity
bit low byte
01 06
F0
0B
01 2C CB
45
And the AC Drive feedback to the upper machine as follows;
Slave
address
Function
code
Parameter
address high byte
Parameter
address low byte
Data
high byte
Data low
byte
CRC Parity
bit high byte
CRC Parity
bit low byte
01 06
F0
0B
01 2C CB
45