200 Series General Purpose Vector AC Drive Chapter 5 Functional Parameter Simple List
33
Chapter 5 Function Parameter Simple List
The function parameters of 200 series AC Drive are organized in groups by functions. And there are 16
groups from F0-FF. Each function group consists of several function codes that are identified by
“Function Group No. + Internal Code Number”. For example, “F2-01” indicates group 2 and its function
code is 1.
☞
Notice 1: It could be used to any load and it should be setup F0-16
、
F0-17
、
F3-00
、
F3-01
、
F3-02.
according to the motor’s nameplate.
☞
Notice 2: 200 type AC Drive factory default is type G (apply to general used load). If the AC Drive is
used as type P with a large gear (used to the fan and water pump load), the function code F0-15 must be
set to 1.
☞
Notice 3: 200 type AC Drive factory default is V/F control. If it needs a big torque on site, F0-14 can be
set to 0 , but F3-00 to F3-02 must be setup according to the motor’s nameplate. Then set F3-08 for motor
parameter auto-learning in the keyboard control channel.
☞
Notice 4: “
√
” Indicates the parameter can be modified, no matter the drive runs or stops; “×” means the
parameter cannot be modified while the drive is running. “
○
” indicates the parameter can be read only.
"*": Remarks with * indicates that there are parameter explanations in Chapter 6.
Function
Code
Name
Setting Scope and Introduction
Factory
Defaults
Modify
Group F0: Basic Running Parameters Group
F0-00
The main frequency
source selection
0: Digital setting, memory after power off
1: Analog V1 setting
2: Analog V2 setting
3: Keyboard potentiometer setting (only for
LCD Keyboard)
4: Multi-segment speed running setting
5: PID control setting
6: Remote communication
setting(communication address 2000H)
7: PLC program running setting
8: HDI high-speed pulse setting(S5)
0
√
F0-01
The auxiliary frequency
source B selection
1
√
F0-02
Auxiliary frequency
source standard selection
when superimposed
0: Relative to maximum frequency
1: Relative to main frequency source
0
√
F0-03
Auxiliary frequency
scope when
superimposed
00
~
150%
100%
√
F0-04
Main and auxiliary
frequency combination
mode
0: Only main frequency setting
1: Only auxiliary frequency setting
2: MF.K or terminal switching selection
3: Main fre auxiliary frequency (the
2
√