Chapter 5 Functional Parameter Simple List 200 Series General Purpose Vector AC Drive
34
direction is decided by main frequency)
4: Main frequency - auxiliary frequency ( the
direction is decided by main frequency)
5: The maximum of both the direction is
decided by main frequency)
6: The minimum of both (the direction is
decided by main frequency)
F0-05
Maximum output
frequency
F0-06(minimum 1.00Hz)
~
300.00Hz
F0-06(minimum 10.0Hz)
~
3000.0Hz
50.00 Hz
×
F0-06
Running frequency upper
limit
F0-07
~
F0-05
50.00 Hz
√
F0-07
Running frequency lower
limit
0.00
~
F0-06
0.00 Hz
√
F0-08
Keypad digital frequency
setting
0.00
~
F0-05
50.00 Hz
√
F0-09
Running direction
setting
0: Forward running
1: Reverse running (Equivalent to motor wire
adjustment)
0 ×
F0-10 Acceleration time 0
0.1
~
3200.0s
Model
depends
√
F0-11 Deceleration time 0
0.1
~
3200.0s
Model
depends
√
F0-12
Operation channel
selection
0: Keyboard start-stop( REMOT off)
1: Terminal start-stop( REMOT on)
2: Communication start-stop( REMOT flash)
0
√
F0-13
Terminal control running
mode
0: Two wire type control 1(The forward
terminal starts and stops in the forward
direction, and the reverse terminal starts and
stops in the reverse direction)
1: Two wire type control 2( The forward
terminal starts and stops, the reverse terminal
changes the direction)
2: Three wire type control 1(Forward terminal
pulse start and stop, reverse terminal selection
direction, three-wire terminal normally closed,
stop when disconnected)
3: Three wire type control 2(Forward terminal
pulse start and stop, reverse terminal pulse start
and stop, three-wire terminal normally closed,
stop when disconnected)
4: Three wire type 3 Forward terminal pulse
starts and stops with forward rotation, reverse
terminal pulse starts and stops with reverse
0 ×
*