200 Series General Purpose Vector AC Drive Chapter 5 Functional Parameter Simple List
39
point 2
F2-06
Multi-point VF voltage
point 2
0.0%
~
100.0%
45.0%
√
*
F2-07
Multipoint VF frequency
point 3
0.00
~
F0-05
35.00Hz
√
*
F2-08
Multi-point VF voltage
point 3
0.0%
~
100.0%
80.0%
√
*
F2-10
V/F Slip compensation
gain
0.0%
~
200.0%
0.0%
√
F2-11
VF Oscillation
suppression gain
0
~
100
It is necessary to increase the gain appropriately
only when the motor oscillates obviously, the
larger the gain, the more obvious the
suppression of oscillation
。
25
√
F2-12
Load loss detection level
(Ball mill broken shaft
detection current)
0.0%
~
150.0%
60.0%
√
F2-13
Load loss detection time
(judgment time for ball
mill shaft broken)
0.0s(no detection)
~
60.0s
it sets to 30.0s special for ball mill
0.0s
√
F2-14
VF overvoltage
excitation gain
0
~
200
During the deceleration of the ac drive, this
parameter can suppress the rise of bus voltage
and avoid over-voltage faults. The larger the
over excitation gain, the stronger the
suppression effect, but it is easy to cause the
output current to increase or the speed to
fluctuate, which needs to be weighed in the
application. For occasions where the inertia is
small, it is recommended to set the over
excitation gain to 0; if there is a braking
resistor, the over excitation gain needs to be set
to 0.
32
√
Group F3: Vector And Torque Control Parameter Group
F3-00 Motor rated power
0.4
~
1000.0kW
Model
depends
×
*
F3-01 Motor rated current
0.1A
~
3200.0A
Model
depends
×
*
F3-02
Motor rated rotating
speed
10
~
32000RPM
Model
depends
×
*
F3-03 Motor resistance of stator
0.001
Ω
~
32.000
Ω
(ac drive power<=55kW)
0.0001
Ω
~
3.2000
Ω
(ac drive power>55kW)
Tuning
parameters
×
*