Heat Manager Pro User Manual V1.5 Page 57
[CH]
Channel number
[SEGM]
Push the value and enter the desired segment number (1-7 for a
programmer and 8 for stopped state/slave/remote)
[PBAND]
Proportional band in degrees (°C/°F).
Default value is 20
[ITIME]
Integral time in seconds.
Default value is 180 seconds
[DTIME]
Differential time in seconds.
Default value is 20 seconds
[TCYC]
Cycle time in seconds.
Default value is 10 seconds for relay outputs.
Set this value to 1.0 second for solid state outputs. This can result in a
better temperature control when using solid state relays instead or normal
mechanical contactors. Don’t set the value to 1.0s with mechanical
contact relays, this will reduce the lifetime of them extensively.
[AT]
Push this button to activate the autotuning. This is only possible when the
setpoint is not increasing/decreasing, so when a programmer is in soak
segment (stable temperature setvalue).
Caution: control output % will
cycle from 100% to 0% a few times, that can result in too high
tempestress on the workpiece.
[BACK]
Go back to the previous screen
[CH 7-12]
Go to the PID settings for channel 7-12
[MAIN MENU]
Go to the main menu