Heat Manager Pro User Manual V1.5 Page 53
Don’t forget to set channels on the slave-Heatmanager Pros to remote in the channel config.
Only then the channel tries to get the setpoint from the master-Heatmanager Pro:
The communication between the master and slave Heatmanager Pros is via ethernet cabling
and/or a switch to interconnect them. Note that the ethernet ports on the touchpanels have a
so-called autosensing port, so crossed cabling is not necessary for operation.
The master Heatmanager Pro must have an IP address of 10.0.0.210.
The IP addresses of the slaves must be set to:
Slave 1:
10.0.10.211
Slave 2:
10.0.10.212
Slave 3:
10.0.10.213
Slave 4:
10.0.10.214
These IP addresses are fixed into the software of the Heatmanager Pro and can therefore be
changed.
If you select a setting the Heatmanager Pro will give advice on how to set the corresponding IP
address must be set. If it is not set correctly the Heatmanager Pro wil give a
n orange “IP not set
correctly” message if it is not correct.