Section 1. Functional Modes
1-17
After the operation is finished ‘
13:0000
’ is displayed. Error 96 indicates that the
Storage Module is not connected or the wrong address was given.
Table 1-11 Transferring a Program using a Storage Module
Key entry
Display
∗
D
13:00
7NA
7N:00
(N is Storage Module address 1-8)
You may now enter one of the following options:
1x
Save Program x to Storage Module (x = 1-8)
2x
Load Program x from Storage Module (x = 1-8)
3x
Erase Program x in Storage Module (x = 1-8)
The CR10X can be programmed on power-up using a Storage Module. Storage
Modules can store up to eight separate programs. If a program is stored as pro-
gram number 8, and if the Storage Module is connected to the CR10X at power-
up, program number 8 is downloaded, compiled and run.
1.8.3 Full/Half Duplex
The *D Mode can also be used to set communications to full or half duplex. The
default is full duplex, which works best in most situations.
Table 1-12 Setting Duplex
Key entry
Display
∗
D
13:00
9A
09:0x
If x=0 the CR10X is set for full duplex
If x=1 the CR10X is set for half duplex
You may now change the option:
0A
Set full duplex
1A
Set half duplex
1.8.4 Set Datalogger ID
Command 8 is used to set the datalogger ID. The ID can be moved to an input
location with Instruction 117 and can then be sampled as part of the data.
Table 1-13 Setting Datalogger ID
Key entry
Display
∗
D
13:00
8A
08:0XXX
Where XXX are zeroes or the current ID. You may
then key in the ID (1-254, excluding 13).