Section 7. Measurement Programming Examples
7-25
Connections
The output of the dew point sensor is measured with a differential voltage
measurement on differential analogue input 4. The CURS100 TIM and dew point
sensor are wired to the CR10X wiring panel as shown in Figure 7-15.
Figure 7-15 Wiring Diagram for CURS100 Terminal Input Module and 4 to
20mA Sensor
Program
01:Volt (Diff) (P2)
1: 1
Reps
2:35
±±±±
2500mV 50Hz Rejection Range
3: 4
DIFF Channel
4: 1
Loc [ Dew_Pnt_C ]
5:.06875 Mult
6:-67.5
Offset
Input Locations
1 Dew_Pnt_C
7.19 SDM Peripherals
The SDM peripherals are measurement and control modules which are controlled
by the CR10X through control ports 1, 2 and 3. The instructions for these
peripherals are:
101 SDM-INT8 8-channel interval timer
102 SDM-SW8 8-channel switch closure multiplexer
103 SDM-A04 4-channel analogue output multiplexer
104 SDM-CD16 16-channel control port expansion module
113 SDM-SI04 4-channel serial interface.
Please consult the SDM peripheral manual for programming examples.
4H
4L
G
12V
G
CR10X
H
L
GND
4 to 20 mA
Sensor
100
Ω
±
0.01%
CURS100 TIM