CR10X Reference Manual
B-2
Clear to Send (CTS)
The sensor uses this line to signal the CR10X that it is ready to receive the pream-
ble or data (see description of parameters 3 and 9 in Section B.2).
B.1.4 Logic Levels
RS232 – Logical 1 is low voltage.
RTS/DTR asserted is high voltage.
TTL
– Logical 1 is high voltage.
RTS/DTR asserted is low voltage.
B.1.5 Parity and Stop Bits
Receive
ASCII and Hexadecimal Pairs in ASCII Representation:
1 start bit, 8 data bits, no parity,
1 stop bit, eighth bit ignored
Binary to decimal equivalent:
1 start bit, 8 data bits, no parity, 1 stop bit
Transmit
1 start bit, 8 data bits, no parity, 1 stop bit
A special version of Instruction 15 is available to enable the CR10X
to receive seven data bits (in addition to the standard eight data
bits). If you have purchased this version, and you select the 7-bit
option, you should amend references to eight data bits in this
manual accordingly.
B.2 Instruction 15 and Parameter Descriptions
PAR.
DATA
NO.
TYPE
DESCRIPTION
01:
2
Repetitions
02:
2
Configuration code (xy)
First Digit (x):
0y ASCII
1y ASCII Hex pair
2y Binary
Second Digit (y):
x0 TTL, 1200 baud
x1 RS232, 1200 baud
x2 TTL, 300 baud
x3 RS232, 300 baud
x4 TTL, 1200 baud, 7-bit
x5 RS232, 1200 baud, 7-bit
x6 TTL, 300 baud, 7-bit
x7 RS232, 300 baud, 7-bit
03:
4
CTS / Delay before send
0 = Wait for Clear to Send
>0 = delay (multiples of .01s)
04:
2
First control port
05:
4
Output start Loc
NOTE