CR10X Reference Manual
C-2
•
Toggle ports and flags
•
Collect newly-stored Final Storage data.
For reading Input or Final Storage data these commands are used as a pair, where
the J command is sent first to configure the datalogger, followed by one or more
K commands which request the data previously specified using the 2413J or
3142J command. If the datalogger time is to be read, or the ports or flags toggled,
then just a single 2413J / 3142J command is used, often followed by another
similar command to set the datalogger up again for subsequent K commands.
A note on datalogger OS versions:
Beginning with Version 1.10 of the CR10X operating system (released October
1999), the datalogger can use either the new 2413J command or the older 3412J
command. Since the J command is not sent with a checksum, the older 3142J
could, over a noisy communications link, be misinterpreted and cause unintended
changes to flags or ports. The advantage of the new version of the J command is
that it does not attempt to set flags or ports; instead, software can use the new U
command which is sent with a checksum to accomplish setting of flags, ports and
input locations. Telecommunications software can determine whether the new J
command is available in a particular datalogger by issuing an A command to
request the datalogger’s status (Section 5, Telecommunications). If the datalogger
version number is reported as V4, the datalogger OS can use the new 2413J, as
well as the new S, T and U commands. See Section 5, Telecommunications, for a
description of these commands.
2413J / 3142J
The format of the command is as follows:
2413J<CR>abcd…
nNULL or 3142J<CR>abcd...nNULL
where
1.
either "2413J<CR>" or "3142J<CR>" is the command.
2.
"a" is a 1 byte value representing the user flags to be toggled. The most
significant bit (MSB), if set, will toggle datalogger user flag 8. Likewise, the
2nd most significant bit, if set, will toggle user flag 7, and so on to the least
significant bit which, if set, toggles user flag 1. Toggle means that if a flag is
set, it will be then reset, or if it is reset, it will be set.
3.
"b" is a 1 byte value whose MSB will determine whether Final Storage Data
is returned after the K command. If the bit is set, Final Storage Data, if any,
will be returned after the next K command. The datalogger initially has this
bit reset upon entering telecommunications, but once set by a J command, it
will remain set until reset by another J command or telecommunications is
terminated.
If the second MSB is set it means a port toggle byte will follow and port
status is to be returned with the K command. Like the MSB, this bit is reset
upon entering telecommunications, but remains set once set until reset by
another J command or telecommunications is terminated.
The third MSB is ignored.
The fourth MSB indicates if the input locations requested by the J command
are 2 byte (B4 set) or 1 byte. In the case of 2 byte locations (most significant