A batch can be canceled (aborted) as follows:
!
Interrupt the batch as described above.
!
While the batch is stopped (the relay is de-energized), use the or
soft buttons to navigate to and highlight the
Total this Batch:
status line. The
CLEAR
soft button replaces the RESUM soft button.
!
Press the
CLEAR
soft button.
!
The value of
Total this Batch:
is cleared to zero.
!
All lines are de-selected and the
START
soft button returns.
!
When the
START
soft button is next pressed,
will dispense and the
Current Batch #:
value increases by one.
The cancelled batch is not re-dispensed.
The flow measured before it was cancelled is not backed out of
Total all Batches:
.
Because flow information is only computed by the flowmeter at the configured display
update interval, the volume dispensed in a batch will typically overshoot the configured
Batch Amount. The relay is de-energized when the measured total equals or exceeds the
batch volume. The degree of overshoot depends on the batch size, the flow rate and the
update interval. You should not configure long update intervals when dispensing small
batches from a high flow rate, as in this situation the overshoot could be a significant
fraction of the batch size.
If the
Batch Start
type is configured as
AUTO,
then operation is as follows:
Immediately upon entering
Run Mode,
the flowmeter accumulates the volume of fluid
flowing in two totalizers associated with the specific
Relay Channel
. If the relay
channel is brought onto the display (using the
RELAY
soft button), the totals are
displayed to the right of the labels
Total this Batch:
and
Total all Batches:
and the
values will be seen to advance.
However, the channel will operate in the manner described
here whether it is on the display or not.
the next batch
Ç
È
!
The relay channel
Status:
is indicated
as
ACTIVE.
!
When the
Total this Batch:
value
reaches the
Batch Amount:
value, the
Current Batch #:
value increases by
one, the
Total this Batch:
value clears
to zero and the relay is energized. Flow
is expected to continue (in this mode,
flow is not controlled by the relay), so
Total this Batch:
immediately starts
increasing again and
Total all Batches:
continues to increase without a break.
!
After the relay has been energized for
the number of seconds shown in the
Relay Timer:
field, it de-energizes
(again, this is not expected to influence
EDIT
Ç
È
RELAY
STOP
Relay #1 Monitor: TOTAL
Status: ACTIVE
Batch Amount:
Current Batch #:
Total all Batches:
Batch Start:
Total this Batch:
5000
32
3296
AUTO
2 T 3.25 in.
[
¢
¢
¢
£
] 1480
Relay Timer: 3
156824526
the fluid flow).
This continues indefinitely (unless the
STOP
soft button is pressed). Each time the
Total
this Batch:
totalizer reaches
Batch Amount:
, it is cleared,
Current Batch #:
advances and
the relay is energized for the time
Relay Timer:
.
In this mode of
Process Control
, the flowmeter is partitioning the flow in the pipe into
batches of a defined amount. Within each batch, it displays the total flow so far for that
batch. It counts the batches. At the end of each batch, the relay energizes for a defined
time period and then de-energizes. An example of what the energized relay might do is to
switch power to a pump or open a valve that results in some other fluid being injected
into the measured fluid stream.
8.2.2
Auto Batch
Start Type