- 36 -
(a) Setting of the number of connecting stations (buffer memory address of master unit : 1H)
Set the number of stations to be connected to master unit such as remote I/O station, remote device
station, intelligent device station, local station (including reserve station).
(b) Setting of station information
(buffer memory address of master unit : the first station(20H)...64th station(5FH))
Set the type of stations to be connected to master unit such as remote I/O station, remote device
station, intelligent device station, local station.
Set for all number of connecting stations.
(bit)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Station type
Station number
Occupied station
1 : occupies 1 station
1(01H)...64(40H)
2 : occupies 2 stations
3 : occupies 3 stations
4 : occupies 4 stations
0:Remote I/O station
1:Remote device station
2:Intelligent device station
ex. Set the Processor to station number 30
[
]
1 4 1 E H
Station number 30(1EH )
(
)
Number of occupied station Processor occupies 4 stations
(
)
Station type
Processor is remote device station
(2) Reading data link condition of processor, remote input (RX)
Create program to interlock after detecting data link condition of processor.
Read RXn0...RX(n+7)F out to M200
M327(M208
M335).
〜
〜
M9036(SM400)
FROM
H0
H680 K4M100
K4
Reading data link condition of processor
FROM
H0
H0E0 K4M200
K8
Read RXn0..RX(n+7)F out to M200...M327
(K4M208)
(M208
M335)
〜
* Example of sequence program for ACPU. Digits for QCPU Q mode , QnACPU are indicated in
.
(
)
( )
<Attention>
Delete the sequence program indicated with broken line part in chart above, in the case of
the following setting is set .
*Using QJ61BT11,AJ61QBT11,A1SJ61QBT11
Set automatic refresh parameter with GX Developer
*Using AJ61BT11,A1SJ61BT11
Set automatic refresh with instruction for CC-Link
(3) Initial setting of processor
Create the program to execute initial setting of processor refer to 6.6 .
(
)
(4) Communication instruction
Create the program to execute identification communication instruction refer to 6.7...6.14 .
(
)
Содержание BIS C-489-1 KBT02 Series