- 14 -
(8) Specifying area for retry count (effective in initial setting only)
Specify retry time that processor BIS C-489 executes instruction when error occurs in data
communication.
: 0 ... 32767 (0 ... 32767 times) ... If the specified number is over 32767, the retry
Specifying range
time would be 32767 times.
: 3
Initial digit
[ex.] Specify retry time to be 5
Retry time
TOP
Hn
K5
K1
○
Store into specifying area for retry time
Head I/O number of master unit
(9) Specifying area for inzone detecting time (valid in initial setting only)
Specifies standby time per 10ms when the code tag gets into communication area to inzone detection
starting communication in executing sequence instruction.
(
)
: 0 ... 32767 (0 ... 327670 ms) ... if the specified number is over 32767, inzone detection
Specifying range
time would be 327670ms
: 0
Initial digit
[ex.] Specify inzone detecting time to be 2 sec.
inzone detecting time
TOP Hn
K200 K1
○
Store specifying area for inzone detecting time
Head I/O number of master unit
Inzone detecting time is;
Standby time since code tag getting into communication area until starting communication.
By specifying this setting, it can communicate with avoiding unstable range.