INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
安装和维护说明手册
D0578-02-ZH
37/100
AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art. 2359 of the Italian Civil Code.
The interlocking device between the disconnector and the earthing switch driven by
different drives is installed on the lower base (Fig. 5A, 5E) and is made of:
由各种不同操作机构驱动的位于隔离开关和接地开关之间的互锁装置被安装于下底座
(图
5A
,
5E)
并由以下装置组成:
•
an interlocking plate (5.23 Fig. 5A, 5E) fixed to the rotary disc (5.12 Fig. 5A, 5E)
on the side of the male arm;
一个被固定在雄刀臂一侧转动盘(图
5A
,
5E
之
5.12
)上的互锁盘(图
5A
,
5E
之
5.23)
;
•
an interlocking cam (5.24 Fig. 5A, 5E) integral with the control lever (5.19 Fig.
5A, 5E) of the earthing switch.
一个与接地开关的控制杆(图
5A
,
5E
之
5.19
)集成的互锁凸轮(图
5A
,
5E
之
5.24
)。
The principle of operation of the interlocking device is shown in Fig. 5C and in Fig.
5F.
互锁装置的工作原理见图
5C
和图
5F
。
6.5
ADJUSTMENT OF THE S2DA / S2DAT DISCONNECTORS
S2DA/S2DAT
隔离开关的调整
In the following sections you can find the procedures for the adjustment and fine
tuning of the equipment.
以下各节里,你将看到的是设备的调整程序和微调程序。
6.5.1 Adjustment of the live part (Fig. 2E, 2F)
过流部件的调整(图
2E
,
2F
)
Carry out a slow CLOSING operation and check that all the male contacts are
centered when they reach the female contacts (Fig. 2E).
执行缓慢合闸的操作并检查当所有雄触头接触到雌触头(图
2E)
时它们都处于中心位
置。
In the CLOSED position, check that the male and female arms complete their travels
(about 90°), they are aligned (tolerance ±2°) and that all the conditions shown in
figures 2E and 2F are met.
在合闸位置时,检查当雄刀臂和雌刀臂完成其行程时(大约
90
°),它们是对准的(
误差±
2
°),而且如图
2E
和
2F
所示的全部条件均得到满足。
Check also that the arms engage for a distance of 25 mm (tolerance -10 / +30), as
shown in figures 2, 2A and 2B.
同样检查雄刀臂和雌刀臂的咬合深度为
25mm(
误差
-10/+30)
,如图
2
,
2A
和
2B
所示
。
With the special crank or lever of the drive of the disconnector, OPEN (with opening
angle 90°±4°) slowly the disconnector and check that the male contacts separate as
shown in figure 2E.
使用专用曲柄或隔离开关操作机构的控制杆,慢慢打开(开闸角度为
90
°±
4
°)隔
离开关并检查雄触头如图
2E
所示的那样分开。
If needed, you can also adjust the upper or lower part of the insulator, thanks to the
freedom of positioning of the fastening holes.