background image

Installer Instructions

WARNING: Failure to follow these instructions could  

result in death, personal injury, or property damage.

•   This circuit breaker is intended for use on single-

phase grounded 120Vac 2-wire branch circuits.  

Shared neutral circuits where the neutral from 

separate branch circuits is combined to one neutral 

wire and returned to either breaker is strictly 

prohibited with this circuit breaker.

•   This equipment must be installed and serviced only 

by a qualified electrician.

WARNING: Turn off power to main breaker before 

beginning installation. Failure to do so will risk 

electrical shock and possible death, personal injury,  

or property damage.

Dual Function Circuit Interrupter (DFCI)  

Installation Instructions
Install the DFCI using the following procedure:

1.   Open the DFCI by moving its handle firmly to the  

OFF position.

2.   Install the DFCI into the load center by plugging  

or bolting the circuit breaker into the desired  

circuit location.

3.   Connect the coiled white “pigtail” wire from the  

DFCI to the panel or enclosure neutral bus terminal 

and secure it tightly. Uncoil pigtail as necessary  

(see connection diagram)

4.   Connect the white (neutral) load wire to the terminal 

side of the circuit breaker, identified by a silver-

colored terminal screw, labeled LOAD NEUTRAL 

5.   Connect black (hot) wire to circuit breaker terminals 

labeled LOAD, identified by a gold-colored terminal 

screw.

6.   Turn on power to main breaker, then close and test 

the DFCI using the test rocker switch on the front of 

the breaker. Follow the Test Procedure indicated in the 

next section.

7.   See Troubleshooting Guides on the next page on how 

totroubleshoot a DFCI.

WARNING: Do not reverse-feed.  Do not subject to 

high-voltage or high-pot tests.  Remove the circuit 

breaker before high-potting occurs on the circuit or  

the system.

D EH41 8 20  H O M EOW N ER  &  I N S TA LLER  I N FO R M ATI O N

Dual Function Circuit Interrupter (DFCI)

Test Procedures (DFCI should be tested regularly, at 

least once per month.)

The test feature allows the homeowner to test the arc 

and ground detection capability by depressing a rocker 

switch in two directions.  The breaker has passed the 

test if the TRIP flag appears in the window.  Use provided 

Test Record Chart DEH41133 to record the dates the 

breaker(s) are tested.

•   

Arc Fault Test: Press the test switch in the direction 

labeled “AF” to check the ability of the DFCI to detect 

high current arcing line-to-neutral or line-to-ground 

and to detect low current arcing in series with the load.

•   

Ground Fault Test: Press the test switch in the 

direction labeled “GF” to check the ability of the DFCI 

to detect ground fault currents.

CAUTION: The DFCI must be supplied with power  

from the load center in order for the tests to function 

properly.

IMPORTANT: If the handle does not move to the  

“TRIP” position when either the AF or GF on the  

“TEST” button is pressed, the DFCI protection is  

not complete. Replace the breaker immediately.

Dual Function Circuit Interrupter

 

NOTE: The neutral pigtail on eMCB’s (AFCI, GFCI and 

DFCI) can be cut to length in the field or extended 

using approved connectors. Additionally, eMCB’s  

with shortened neutrals can be installed as shown 

providing a fast and clean installation.

Dual 

Function 

Circuit

LED/Trip Flag

Test Button

120Vac 

Duplex 

Receptacle

Load 

Power 

Wire 

(Black)

Load 

Neutral 

Wire 

(White)

Short White Wire 

Connects to Load 

Center Neutral

Содержание DEH41820

Страница 1: ...ee Troubleshooting Guides on the next page on how totroubleshoot a DFCI WARNING Do not reverse feed Do not subject to high voltage or high pot tests Remove the circuit breaker before high potting occurs on the circuit or the system DEH41820 HOMEOWNER INSTALLER INFORMATION Dual Function Circuit Interrupter DFCI Test Procedures DFCI should be tested regularly at least once per month The test feature...

Страница 2: ...esolve the issue the breaker may have lost its ground fault sensing capability due to a sensing circuit failure 1 Remove the load s neutral wire from the breaker 2 Reset the breaker by switching it OFF and then ON 3 If the breaker does not trip a short circuit ground fault or grounded neutral must be cleared from the downstream circuit 4 If the breaker trips replace breaker The circuit breaker is ...

Страница 3: ...de alto voltaje o de alta potencia Remueva el cortacircuitos antes de que ocurra un evento de alta potencia en el circuito o en el sistema eléctrico DEH41820 INFORMACIÓN PAR A EL PROPIETARIO Y EL INSTAL ADOR Interruptor de Función Doble Procedimientos de prueba El DFCI debe probarse con una frecuencia de al menos una vez por mes La función de prueba del cortacircuitos permite al propietario probar...

Страница 4: ...a es posible que el cortacircuitos haya perdido la capacidad de detectar fallas a tierra debido a una falla en el circuito de detección 1 Remueva el cable neutral de la carga del cortacircuitos 2 Restablezca el cortacircuitos moviendo la manija a la posición de apagado OFF y luego moviéndola a la posición de encendido ON 3 Si el cortacircuitos no interrumpe un corto circuito una falla a tierra o u...

Страница 5: ...ISSEMENT Ne pas inverser l alimentation Ne pas soumettre à de tests de haute tension ou de haut voltage Enlevez le disjoncteur avant que la haute tension ne se produise dans le circuit ou le système DEH41820 INFORMATIONS POUR LE PROPRIÉTAIRE ET L INSTALL ATEUR Disjoncteur double fonction Dual Function Circuit Interrupter DFCI Procédures de test Les DFCI devraient être régulièrement testés au moins...

Страница 6: ...e à cause d une défaillance du circuit de détection 1 Enlevez le fil de charge neutre du disjoncteur 2 Réinitialisez le disjoncteur en le basculant sur OFF puis sur ON 3 Si le disjoncteur ne se déclenche pas il faut débloquer un court circuit un défaut de terre ou un sol neutre du circuit en aval 4 Si le disjoncteur se déclenche remplacez le disjoncteur Le disjoncteur clignote constamment ROUGE et...

Отзывы: