![Areva S2DA Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/areva/s2da/s2da_instruction-for-installation-and-maintenance_2967199045.webp)
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
安装和维护说明手册
D0578-02-ZH
45/100
AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art. 2359 of the Italian Civil Code.
PREVENTIVE MAINTENANCE PLAN OF SWITCHGEARS
GUARANTEED UP TO 3,000 OPERATIONS
保证操作次数为
3000
次的开关设备预防性维护计划
3
SWITCHGEAR IN SERVICE
IN SERVICE
MINOR INSPECTION
min. every 3 years
OUT OF SERVICE
Compliant?
?
NO
YES
CORRECTION
6
/
1500
INSPECTION
every 6 years / 1500
operations
Compliant?
?
NO
YES
12
/
3000
MAJOR INSPECTION
every 12 years /
3000 operations
OUT OF SERVICE
CORRECTION
PREVENTIVE MAINTENANCE PLAN OF SWITCHGEARS
GUARANTEED UP TO 10,000 OPERATIONS
保证操作次数为
10000
次的开关设备预防性维护计划
4
SWITCHGEAR IN SERVICE
IN SERVICE
MINOR INSPECTION
min. every 4 years
OUT OF SERVICE
Compliant?
?
NO
YES
CORRECTION
8
/
5000
INSPECTION
every 8 years /
5000 operations
Compliant?
?
NO
YES
15
/
10000
MAJOR INSPECTION
every 15 years /
10000 operations
OUT OF SERVICE
CORRECTION