![Areva S2DA Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/areva/s2da/s2da_instruction-for-installation-and-maintenance_2967199044.webp)
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
安装和维护说明手册
D0578-02-ZH
44/100
AREVA T&D S.p.A. – Via Meucci, 22 30020 Noventa di Piave (VE) ITALY – Tel. : 39 0421 309511 – Fax : 39 0421 65254
Subsidiary of AREVA T&D Italy SpA (AREVA group) with registered office in Via Meucci, 22 30020 Noventa di Piave (VE) - ITALY, under Art. 2359 of the Italian Civil Code.
PREVENTIVE MAINTENANCE PLAN OF SWITCHGEARS
GUARANTEED UP TO 1,000 OPERATIONS
保证操作次数为
1000
次的开关设备预防性维护计划
SWITCHGEAR IN SERVICE
IN SERVICE
MINOR INSPECTION
min. every 2 years
OUT OF SERVICE
Compliant?
?
NO
YES
CORRECTION
5
/
500
INSPECTION
every 5 years /
500 operations
Compliant?
?
NO
YES
10
/
1000
MAJOR INSPECTION
every 10 years /
1000 operations
OUT OF SERVICE
CORRECTION
PREVENTIVE MAINTENANCE PLAN OF SWITCHGEARS
GUARANTEED UP TO 2,000 OPERATIONS
保证操作次数为
2000
次的开关设备预防性维护计划
SWITCHGEAR IN SERVICE
IN SERVICE
MINOR INSPECTION
min. every 2 years
OUT OF SERVICE
Compliant?
?
NO
YES
CORRECTION
5
/
1000
INSPECTION
every 5 years /
1000 operations
Compliant?
?
NO
YES
10
/
2000
MAJOR INSPECTION
every 10 years /
2000 operations
OUT OF SERVICE
CORRECTION