Instruction manual –AQ F210 Feeder Protection IED
174 (292
)
3.
Circuit breaker is opened and I> Start signal is released and simultaneously REQ1
signal for autorecloser is released. Recloser starts to calculate the Shot1 Dead Time for
closing the breaker.
4.
Dead Time for Shot1 is exceeded and autorecloser sends close request for the Object
breaker, the close conditions are met and the breaker close command is sent to breaker
close coil.
5.
Circuit breaker is closed and since fault is not cleared by the Shot1 given non-energized
time, pick-up of I> is detected. Close command is drop off after the breaker closed
indication is received and the autorecloser starts to calculate Reclaim time for Shot1
simultaneously with the arcing time.
6.
Arcing time for the Shot1 is exceeded which means that the fault is not cleared and the
recloser sends open command to the breaker. Recloser enters to the Shot2 state.
7.
Circuit breaker opens and the Dead time calculation for Shot2 starts.
8.
Shot2 Dead time calculation is finished and the recloser sends close command to the
breaker.
9.
Circuit breaker is closed and since fault cleared by the Shot2 given non-energized time,
no pick-ups are detected. Close command is drop off after the breaker closed indication
is received and the autorecloser starts to calculate Reclaim time for Shot2.
10.
Reclaim Time for Shot2 is exceeded and the reclosing cycle is ended. AR running,
Shot2 Running and REQ1 Running signals are reset and Reclaim Time for the
Autorecloser application starts. Difference in between of the autoreclosing and shot
specific reclaim times is that if fault is returning in shot specific reclaim time autorecloser
jumps to next shot. If a fault return after successful cycle and Autoreclosing reclaim time
is running recloser will go directly to final trip state and lock-out state. This behavior can
be controlled with settings of the recloser. Both of these reclaim times can be set to 0
when they are not needed. Recloser function will skip all timers set to 0. Also is possible
to set the AR Reclaim not to be used after successful reclosing cycle.
11.
Autoreclosing Reclaim Time is exceeded and Autorecloser is set to Ready state waiting
for next request.
4.3.3.8
A
UTORECLOSING SEQUENCE FROM
S
TART WITH TWO SHOT
,
HIGH SPEED
SUCCEEDS
The Scheme for autoreclosing starter and shots is the same than in the previous examples
with same settings and signals. In this example fault is cleared by the high speed
autoreclosing.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...