Instruction manual –AQ F210 Feeder Protection IED
131 (292
)
Table 4.2.8.2-63 Environmental settings
Name
Range
Step
Default
Description
Object max temp (tmax =
100%)
0…500 deg
1 deg
90
Maximum allowed temperature for
the protected object. Default setting
is +90 degrees and it suits for
Celsius range and for PEX
insulated cables
Ambient temp sel
0: Manual set
1: RTD
-
0:Manual
set
Selection whether fixed or
measured ambient temperature
should be used for the thermal
image biasing.
Man.Amb.Temp.Set
0…500 deg
1 deg
15 deg
Manual fixed ambient temperature
setting for the thermal image
biasing. For underground cables
commonly is used 15 degrees
Celsius. Setting is visible if Ambient
temp sel is set to “Manual set”.
RTD Amb.Temp.Read
0…500 deg
1 deg
15 deg
RTD ambient temperature reading
for the thermal image biasing.
Setting is visible if Ambient temp sel
is set to “RTD”.
Ambient lin. or curve
0:Linear est.
1:Set curve
-
0:Linear
est
Selection of ambient temperature
correction either by internally
calculated compensation based into
end temperatures or user settable
curve. Default setting is 0:Linear
corr, which means internally
calculated correction for ambient
temperature.
Temp.reference (tref)
k
amb
=1.0
-60…500 deg
1 deg
15 deg
Temperature reference setting. In
this temperature manufacturer
presumptions apply and the thermal
correction factor is 1.00 (rated
temperature). For ground dug
cables this is usually 15 ̊C and in
air 25 ̊C.
Setting is visible if Ambient lin. or
curve is set to “Linear est.”
Max ambient temp
0…500 deg
1 deg
45 deg
Maximum ambient temperature
setting. If measured temperature is
more than maximum set
temperature the set correction
factor for maximum temperature
shall be used. Setting is visible if
Ambient lin. or curve is set to
“Linear est.”
k at max amb temp
0.01…5.00 xIn
0.01 xIn 1.00 xIn
Temperature correction factor for
maximum ambient temperature
setting. Setting is visible if Ambient
lin. or curve is set to “Linear est.”
Min ambient temp
-60…500 deg
1 deg
0 deg
Minimum ambient temperature
setting. If measured temperature is
less than minimum set temperature
the set correction factor for
minimum temperature shall be
used. Setting is visible if Ambient
lin. or curve is set to “Linear est.”
k at min amb temp
0.01…5.00 xIn
0.01 xIn 1.00 xIn
Temperature correction factor for
minimum ambient temperature
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...