Instruction manual –AQ F210 Feeder Protection IED
30 (292
)
CONNECTIONS-menu
IP address of the IED is user settable.
Default IP-address varies from device to
another.
Network subnet mask is entered here.
Gateway is configured only when
communicating with IEDs in separate subnet.
Bitrate of the RS-485 serial communication
interface is 9600 bps as standard but can be
changed to 19200 or 38400 bps in case the
external device supports faster speed.
Databits, parity and stopbits can be set
according the connected external devices.
As default the IED does not have any serial
protocol activated (None) but IEC103,
ModbusIO and Modbus RTU can be used for
communication.
Figure 3.2.2.4-30 AQ-200 series IED Connections sub- menu.
Note! When communicating with IED via front Ethernet port the IP address is always
192.168.66.9.
SNTP protocol is used for time
synchronization over Ethernet. It can be used
at the same time with ModbusTCP and
IEC61850 protocols.
ModbusTCP can be used at the same time
with other Ethernet based protocols like
SNTP and IEC61850.
ModbusRTU / IEC103 / ModbusIO
configuration menus. ModbusRTU like other
serial protocols can be used only one at the
time over one physical serial communication
interface.
Figure 3.2.2.4-31 AQ-200 series IED Protocols sub- menu.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...