Instruction manual –AQ F210 Feeder Protection IED
191 (292
)
Figure 4.3.4-84 Simplified function block diagram of the CLPU function.
4.3.4.1
M
EASURED INPUT VALUES
Function block uses analog current measurement values. Function block always utilizes
peak-to-peak measurement from samples and by user selection the monitored magnitude
can be either fundamental frequency RMS values, True RMS values from the whole
harmonic specter of 32 components or peak to peak values. -20ms averaged value of the
selected magnitude is used for pre-fault data registering.
Table 4.3.4.1-90 Analogic magnitudes used by the CLPU function.
Signal
Description
Time base
IL1RMS
Fundamental RMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental RMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental RMS measurement of phase L3/C current
5 ms
Selection of the used AI channel is made with a setting parameter. In all possible input
channel variations pre-fault condition is presented with 20 ms averaged history value from
-20 ms of Start or Trip event.
4.3.4.2
P
ICK
-
UP CHARACTERISTICS
Pick-up and activation of the CLPU function is controlled by
ILow, IHigh and IOver
setting
parameters, which defines the maximum and minimum allowed measured current before
action from the function. The function constantly calculates the ratio in between of the
setting values and measured magnitude (Im) per all three phases. Reset ratio of 97 % is
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...