Instruction manual –AQ F210 Feeder Protection IED
96 (292
)
4.2.6
C
IRCUIT BREAKER FAILURE PROTECTION
(CBFP)
(50BF)
Circuit breaker failure protection (CBFP) function is used for monitoring the circuit breaker
operation after it has been tripped. CBFP function can be used for Retrip to the failing
breaker and if the Retrip fails the upstream breaker can be tripped by using CBFP output.
Retrip functionality can be disabled if the breaker does not have two open coils.
CBFP function can be triggered from overcurrent (phases and residual), digital output- or
input monitor or combination of these mentioned triggers.
In current dependent mode CBFP function measures constantly phase current magnitudes
and selected residual current. In binary input dependent mode any of the IED binary input
can be used for triggering the CBFP. In binary output dependent mode CBFP monitors
selected output relay control signal status. Blocking signal and setting group selection
controls the operating characteristics of the function during normal operation.
Outputs of the function are RETRIP, CBFP and Blocked signals. Setting parameters are
static inputs for the function which are changed only by user input in the setup phase of the
function. CBFP function utilizes total of eight separate setting groups which can be selected
from one common source. Also the operating mode of the CBFP can be changed by setting
group selection.
The operational logic consists of input magnitude processing, threshold comparator, block
signal check, time delay characteristics and output processing.
Inputs for the function are setting parameters and measured and pre-processed current
magnitudes and binary input and output signals. Function output signals can be used for
direct IO controlling and also for user logic programming. The function registers its operation
into 12 last time-stamped registers and also generates general time stamped ON/OFF
events to the common event buffer from each of the two output signal. Time stamp
resolution is 1ms. Function provides also cumulative counters for RETRIP, CBFP and
BLOCKED events.
In the following figure is presented the simplified function block diagram of the CBFP
function.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...