Instruction manual –AQ F210 Feeder Protection IED
20 (292
)
C
ONTROLS
E
NABLED
Activation of different control functions is
done in Controls Enabled –sub menu. Each
control function is disabled as standard.
Active functions will appear below Control
Functions –sub menu.
Activated objects will appear below Objects –
sub menu. Each object is disabled as
standard.
Figure 3.2.2.3-15 AQ-200 series IED Controls Enabled sub- menu.
S
ETTING
G
ROUPS
Active setting group displays the current
active setting group 1…8.
It is possible to activate desired setting group
by setting the force SG. While doing this
Force SG change has to be enabled.
In Used setting groups menus it is possible
to activate setting groups between 1 and
1…8 (default only 1 group is active).
Select local control for different setting
groups from SG Local Select. Digital inputs,
Logical inputs or outputs, stage starting-
tripping- or blocking, RTDs and object status
information can be used.
Event masking for setting groups (masks are
off as default). Only masked events appear
to event list. Events cannot be cleared.
Figure 3.2.2.3-16 Setting Groups menu displays all the information related to group
changing.
Setting group 1 has the highest and group 8 the lowest priority. Setting groups can be
controlled with steady signal or pulses.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...