Instruction manual –AQ F210 Feeder Protection IED
78 (292
)
Table 4.2.3.4-32 Operating time characteristics setting parameters.
Name
Range
Step
Default
Description
Delay Type
DT
IDMT
-
DT
Selection of the delay type time counter.
Selection possibilities are dependent
(IDMT, Inverse Definite Minimum Time)
and independent (DT, Definite Time)
characteristics.
Definite operating
time delay
0.000…1800.000 s 0.005 s
0.040 s
Definite time operating delay. Setting is
active and visible when Delay Type is
selected to DT.
When set to 0.000 s the stage operates as
instant (PIOC, 50) stage without added
delay. When the parameter is set to 0.005
– 1800 s the stage operates as
independent delayed (PTOC, 51).
Delay curve series IEC
IEEE
-
IEC
Setting is active and visible when Delay
Type is selected to IDMT.
Delay curve series for IDMT operation
following either IEC or IEEE/ANSI
standard defined characteristics.
Delay
characteristics
IEC
NI
EI
VI
LTI
Param
-
NI
Setting is active and visible when Delay
Type is selected to IDMT.
IEC standard delay characteristics.
Normally Inverse, Extremely Inverse, Very
Inverse and Long Time Inverse
characteristics. Param selection allows the
tuning of the constants A and B which
allows setting of characteristics following
the same formula as the IEC curves
mentioned here.
Delay
characteristics
IEEE
ANSI NI
ANSI VI
ANSI EI
ANSI LI
IEEE MI
IEEE VI
IEEE EI
Param
-
LTI
Setting is active and visible when Delay
Type is selected to IDMT.
IEEE and ANSI standard delay
characteristics. ANSI: Normal Inverse,
Very Inverse, Extremely inverse, Long
time inverse characteristics. IEEE:
Moderately Inverse, Very Inverse,
Extremely Inverse characteristics. Param
selection allows the tuning of the
constants A, B and C which allows setting
of characteristics following the same
formula as the IEEE curves mentioned
here.
Time dial setting k 0.01…25.00 s
0.01 s
0.05 s
Setting is active and visible when Delay
Type is selected to IDMT.
Time dial / multiplier setting for IDMT
characteristics.
A
0.0000…250.0000
0.0001
0.0860
Setting is active and visible when Delay
Type is selected to IDMT.
Constant A for IEC/IEEE characteristics.
B
0.0000…5.0000
0.0001
0.1850
Setting is active and visible when Delay
Type is selected to IDMT.
Constant B for IEC/IEEE characteristics.
C
0.0000…250.0000
0.0001
0.0200
Setting is active and visible when Delay
Type is selected to IDMT.
Constant C for IEEE characteristics.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...