Instruction manual –AQ F210 Feeder Protection IED
167 (292
)
4.3.3.4
A
UTORECLOSING SEQUENCE FROM
T
RIP WITH TWO SHOT
,
HIGH SPEED
FAILS AND TIME DELAYED SUCCEEDS
The Scheme for autoreclosing starter and shots is the same than in the previous example
with same settings and signals. In this example fault persist for the high speed autoreclosing
but is cleared by time delayed autoreclosing.
Figure 4.3.3.4-71 Settings for earth fault reclosing with two shots.
This type of sequence represents 10-15% of all the faults in the medium voltage overhead
line network.
Figure 4.3.3.4-72 Signal status graph of the semi-permanent earth fault autoreclosing
cycle.