Instruction manual –AQ F210 Feeder Protection IED
193 (292
)
4.3.4.4
O
PERATING TIME CHARACTERISTICS FOR ACTIVATION AND RESET
The operating timers’ behavior of the function can be set for activation and the cold load
pick up situation monitoring and release.
In the Table 4.2.1.3-22 are presented the setting parameters for the function time
characteristics.
Table 4.3.4.4-92 Operating time characteristics setting parameters.
Name
Range
Step
Default
Description
Tset
0.000…1800.000s 0.005s 10.000s CLPU start timer, this setting defines how long the ILow
condition has to last before CLPU is activated.
Tmax
0.000…1800.000s 0.005s 30.000s CLPU max timer, this setting defines how long the
starting condition can last and the current is allowed to
be over IHigh.
Tmin
0.000…1800.000s 0.005s 0.040s
CLPU min timer, this setting defines how long the
starting condition last for minimum time. In case if the
start up sequence includes more than one inrush
situation this parameter may be used to prolong the
CLPU time over the first inrush. Also this parameter
operates as “reclaim” time for the CLPU function in case
the inrush current is not immediately initiated in the start-
up sequence.
In following figures are presented few typical cases of CLPU situations.
Figure 4.3.4.4-85 Example of timers and pick-up parameters. Normal CLPU situation.
CLPU activates after current has been under
ILow
setting for time
Tset .
When current
exceed the IHigh setting the maximum allowed CLPU timer start to count until
Tmax
time.
In this example the pick-up current is cleared before the
Tmax
time. When the measured
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...