Instruction manual –AQ F210 Feeder Protection IED
47 (292
)
I02 CT secondary
0.1…10.0 A
0.1A
5.0A
Rated secondary current of the CT in
amperes.
I02 Polarity
0:-
1:Invert
-
0:-
I02 (fine residual) measurement channel
polarity (direction) selection. Default
setting is that positive current flow is from
connector 9 to connector 10.
CT scaling factor P/S -
-
-
IED feedback value, this is the calculated
scaling factor for primary /secondary
current ratio
4.1.1.4
M
EASUREMENTS
Following measurements are available from the measured current channels.
Table 4.1.1.4-8 Per unit phase current measurements in AQ-2xx.
Name
Range
Step
Description
Phase current ILx
0.00…1250.0 xIn
0.01xIn
Per unit measurement from each phase
current channel fundamental frequency
RMS current.
Phase current ILx TRMS
0.00…1250.0 xIn
0.01xIn
Per unit measurement from each current
channel TRMS current including
harmonics up to 31
st
.
Peak to peak current ILx
0.00…500.0 xIn
0.01xIn
Per unit measurement peak to peak
current from each phase current
measurement channel.
Table 4.1.1.4-9 Primary phase current measurements in AQ-2xx.
Name
Range
Step
Description
Primary Phase current
ILx
0.00…1000000.0A
0.01A
Primary measurement from each phase
current channel fundamental frequency
RMS current.
Phase current ILx TRMS
pri
0.00…1000000.0A
0.01A
Primary measurement from each current
channel TRMS current including
harmonics up to 31
st
.
Table 4.1.1.4-10 Secondary phase current measurements in AQ-2xx.
Name
Range
Step
Description
Secondary Phase current
ILx
0.00…300.0A
0.01A
Secondary measurement from each
phase current channel fundamental
frequency RMS current.
Phase current ILx TRMS
sec
0.00…300.0A
0.01A
Secondary measurement from each
current channel TRMS current including
harmonics up to 31
st
.
Table 4.1.1.4-11 Phase current angles measurements in AQ-2xx.
Name
Range
Step
Description
Phase angle ILx
0.00…360.00 deg
0.01deg Phase angle measurement of the three
phase current inputs.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...