Instruction manual –AQ F210 Feeder Protection IED
273 (292
)
H
ARMONIC
OC
(50H/51H,
68)
I
H
>,
I
H
>>,
I
H
>>>,
I
H
>>>>
Input signals
Input magnitudes
Phase current IL1/IL2/IL3 TRMS
Residual current I01 TRMS
Residual current I02 TRMS
Pick-up
Harmonic selection
2nd, 3rd, 4th, 5th, 7th, 9th, 11th, 13th, 15th, 17th or 19th
Used magnitude
Harmonic per unit xIn
Harmonic relative Ih/IL
Pick-up setting
0.05…2.00 x In, setting step 0.01 x In (xIn)
5.00…200.00 %, setting step 0.01 % (Ih/IL)
Inaccuracy
-Starting xIn
-Starting xIh/IL
<0.03 xIn (2nd, 3rd, 5th)
<0.03 xIn tolerance to Ih (2nd, 3rd, 5th)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy
-Definite Time (Im/Iset ratio >1.05)
±1.0 % or ±30 ms
IDMT operating time setting (ANSI / IEC)
0.02…1800.00 s, setting step 0.001 x parameter
IDMT setting parameters
k
Time dial setting for IDMT
A
IDMT Constant
B
IDMT Constant
C
IDMT Constant
0.01…25.00
step 0.01
0…250.0000
step 0.0001
0…5.0000
step 0.0001
0…250.0000
step 0.0001
Inaccuracy
-IDMT operating time
-IDMT minimum operating time; 20 ms
±1.5 % or ±20 ms
±20 ms
Instant operation time
Start time and instant operation time (trip):
(Im/Iset ratio >1.05)
<50 ms
Reset
Reset ratio
95 % of pick-up setting
Reset time setting
Inaccuracy: Reset time
0.010 … 10.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
Note!
-Harmonics generally: Amplitude of harmonic content has to be least 0.02 x In
when relative (Ih/IL) mode is used.
-Blocking: To achieve fast activation for blocking purpose with harmonic OC
stage the harmonic stage may activate if rapid load change or fault situation
occur. Intentional activation lasts for about 20 ms if harmonic component is not
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...