Instruction manual –AQ F210 Feeder Protection IED
270 (292
)
9.2
P
ROTECTION FUNCTIONS
All specified operation times include mechanical trip contact delay.
9.2.1
C
URRENT PROTECTION FUNCTIONS
O
VERCURRENT
(50/51)
I>,
I>>,
I>>>,
I>>>>
Input signals
Input magnitudes
Phase current fundamental freq RMS
Phase current TRMS
Phase current peak-to-peak
Pick-up
Pick-up current setting
0.10…40.00 x In, setting step 0.01 x In
Inaccuracy
-Current
±0.5 %I
SET
or ±15 mA (0.10…4.0 x I
SET
)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy
-Definite Time (Im/Iset ratio > 3)
-Definite Time (Im/Iset ratio 1.05…3)
±1.0 % or ±20 ms
±1.0 % or ±30 ms
IDMT operating time setting (ANSI / IEC)
0.02…1800.00 s, setting step 0.001 x parameter
IDMT setting parameters
k
Time dial setting for IDMT
A
IDMT Constant
B
IDMT Constant
C
IDMT Constant
0.01…25.00
step 0.01
0…250.0000
step 0.0001
0…5.0000
step 0.0001
0…250.0000
step 0.0001
Inaccuracy
-IDMT operating time
-IDMT minimum operating time; 20 ms
±1.5 % or ±20 ms
±20 ms
Instant operation time
Start time and instant operation time (trip):
(Im/Iset ratio > 3)
(Im/Iset ratio 1.05…3)
<35 ms (typically 25 ms)
<50 ms
Reset
Reset ratio
97 % of pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.010 … 10.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...