Instruction manual –AQ F210 Feeder Protection IED
233 (292
)
Table 4.4.6.5-118. Event codes of the THD function
In the register of the THD function is recorded activated, blocked etc. “On” event process
data. In the table below is presented the structure of THD function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 4.4.6.5-119. Register content.
Date & Time
Event
code
IL1
THD
IL2
THD
IL3
THD
I01
THD
I02
THD
Ph
Trem
I01
Trem
I02
Trem
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
3521-
3534
Descr.
Measured THD values on the
trigger event.
Time left to Alarm on
the trigger event
1 - 8
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
3521
55 THD1
1 THD Start Phase On
1
3522
55 THD1
2 THD Start Phase Off
0
3523
55 THD1
3 THD Start I01 On
1
3524
55 THD1
4 THD Start I01 Off
0
3525
55 THD1
5 THD Start I02 On
1
3526
55 THD1
6 THD Start I02 Off
0
3527
55 THD1
7 THD Alarm Phase On
1
3528
55 THD1
8 THD Alarm Phase Off
0
3529
55 THD1
9 THD Alarm I01 On
1
3530
55 THD1
10 THD Alarm I01 Off
0
3531
55 THD1
11 THD Alarm I02 On
1
3532
55 THD1
12 THD Alarm I02 Off
0
3533
55 THD1
13 Blocked On
1
3534
55 THD1
14 Blocked Off
0
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...