![Arcteq AQ-F210 Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/arcteq/aq-f210/aq-f210_instruction-manual_2964940052.webp)
Instruction manual –AQ F210 Feeder Protection IED
52 (292
)
As can be noted generally that the frequency dependent sampling improves the
measurement accuracy significantly also there can be seen that the measurement hardware
is not linear considering the measured analog signal frequency. For this reason the
magnitude and angle measurements need to be calibrated against frequency. For this
purpose measured channels FFT result fundamental frequency component is corrected for
magnitude and angle errors by Arcteq AQ-2xx series patented calibration algorithms.
4.1.2.1
T
ROUBLESHOOTING
It is possible that for some reason the measured currents may not be as expected. For
these cases following checks may be helpful.
Problem
Check / Resolution
Measured current or voltage amplitude is too low
compared to what it should be. Values are “jumping”
and are not stable.
Set system frequency may be wrong. Check the set
frequency and that it matches to your local system
frequency or change the measurement mode to
“Tracking” and the IED will adjust the frequency by
itself.
Frequency readings are wrong.
In tracking mode frequency interpreted by the relay
may be wrong if there is no current/voltage injected to
the CT or VT. Check the frequency measurement
settings.
4.1.2.2
S
ETTINGS
Table 4.1.2.2-21 Settings of the frequency tracking in AQ-2xx.
Name
Range
Step
Default
Description
Sampling mode
0:Fixed
1:Tracking
-
0:Fixed
Selection of the IED measurement
sampling mode either fixed user settable
frequency or tracked system frequency
System nominal
frequency
5…75Hz
1Hz
50Hz
User settable system nominal frequency
Tracked system
frequency
5…75.0Hz
0.1Hz
-
Display of rough measured system
frequency
Sampl.freq. used
5…75.0Hz
0.1Hz
-
Display of used tracking frequency at the
moment
Freq.Reference 1
0:None
1:CT1IL1
2:CT2IL1
3:VT1U1
4:VT2U1
-
CT1IL1
Frequency tracking reference 1
Freq.Reference 2
0:None
1:CT1IL2
2:CT2IL2
3:VT1U2
4:VT2U2
-
CT1IL2
Frequency tracking reference 2
Freq.Reference 3
0:None
-
CT1IL3
Frequency tracking reference 3
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...