Instruction manual –AQ F210 Feeder Protection IED
82 (292
)
Figure 4.2.4-24 Simplified function block diagram of the CUB function.
4.2.4.1
M
EASURED INPUT VALUES
Function block uses analog current measurement values. Function block utilizes calculated
positive and negative sequence currents. In broken conductor mode (I2/I1) also the phase
currents RMS value is used for the minimum current check. Zero sequence and the
component sequence angles are used for the fault registering and for fault analysis
processing. -20ms averaged value of the selected magnitude is used for pre-fault data
registering.
Table 4.2.4.1-36 Analogic magnitudes used by the CUB function.
Signal
Description
Time base
I1
Positive sequence current magnitude
5 ms
I2
Negative sequence current magnitude
5 ms
IZ
Zero sequence current magnitude
5 ms
I1 ANG
Positive sequence current angle
5 ms
I2 ANG
Negative sequence current angle
5 ms
IZ ANG
Zero sequence current angle
5 ms
IL1RMS
Phase L1 (A) measured RMS current
5 ms
IL2RMS
Phase L2 (B) measured RMS current
5 ms
IL3RMS
Phase L3 (C) measured RMS current
5 ms
Selection of the used AI channel is made with a setting parameter. In all possible input
channel variations pre-fault condition is presented with 20 ms averaged history value from
-20 ms of Start or Trip event.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...