Instruction manual –AQ F210 Feeder Protection IED
90 (292
)
Table 4.2.5.1-42 Analogic magnitudes used by the HOC function.
Signal
Description
Time base
IL1FFT
Magnitudes (rms) of phase L1/A current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
IL2FFT
Magnitudes (rms) of phase L2/B current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
IL3FFT
Magnitudes (rms) of phase L3/C current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
I01FFT
Magnitudes (rms) of residual I01 current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
I02FFT
Magnitudes (rms) of residual I02 current components:
Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
5 ms
Selection of the used AI channel and monitored harmonic as well as per unit monitoring or
percentage of fundamental monitoring is made with a setting parameter. In all possible input
channel variations pre-fault condition is presented with 20 ms averaged history value from
-20 ms of Start or Trip event.
4.2.5.2
O
PERATING MODE AND INPUT SELECTION
The function can be set to monitor the ratio of the measured harmonic to the measured
fundamental component or directly the per unit value of the harmonic current. Also the user
needs to select the correct measurement input.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...