Instruction manual –AQ F210 Feeder Protection IED
110 (292
)
Figure 4.2.7-37 Simplified function block diagram of the REF function.
4.2.7.1
M
EASURED INPUT VALUES
Function block uses analog current measurement values. Function uses the fundamental
frequency magnitude of the current measurement inputs and calculated residual current
with residual current measurement. For residual current measurement I01 or I02 can be
selected.
Table 4.2.7.1-55 Analogic magnitudes used by the REF function.
Signal
Description
Time base
IL1RMS
Fundamental RMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental RMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental RMS measurement of phase L3/C current
5 ms
I01RMS
Fundamental RMS measurement of residual input I01
5 ms
I02RMS
Fundamental RMS measurement of residual input I02
5 ms
IL1Ang
Fundamental angle of phase L1/A current
5 ms
IL2 Ang
Fundamental angle of phase L2/B current
5 ms
IL3 Ang
Fundamental angle of phase L3/C current
5 ms
I01 Ang
Fundamental angle of residual input I01
5 ms
I02 Ang
Fundamental angle of residual input I02
5 ms
Selection of the used residual current input AI channel is made with a setting parameter.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...