![Arcteq AQ-F210 Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/arcteq/aq-f210/aq-f210_instruction-manual_2964940073.webp)
Instruction manual –AQ F210 Feeder Protection IED
73 (292
)
Table 4.2.2.5-28. Event codes of the NOC function instances 1 – 4.
Event
Number
Event
channel
Event block name
Event
Code
Description
Event
Type
1280
20 NOC1
0 Start ON
1
1281
20 NOC1
1 Start OFF
0
1282
20 NOC1
2 Trip ON
1
1283
20 NOC1
3 Trip OFF
0
1284
20 NOC1
4 Block ON
1
1285
20 NOC1
5 Block OFF
0
1344
21 NOC2
0 Start ON
1
1345
21 NOC2
1 Start OFF
0
1346
21 NOC2
2 Trip ON
1
1347
21 NOC2
3 Trip OFF
0
1348
21 NOC2
4 Block ON
1
1349
21 NOC2
5 Block OFF
0
1408
22 NOC3
0 Start ON
1
1409
22 NOC3
1 Start OFF
0
1410
22 NOC3
2 Trip ON
1
1411
22 NOC3
3 Trip OFF
0
1412
22 NOC3
4 Block ON
1
1413
22 NOC3
5 Block OFF
0
1472
23 NOC4
0 Start ON
1
1473
23 NOC4
1 Start OFF
0
1474
23 NOC4
2 Trip ON
1
1475
23 NOC4
3 Trip OFF
0
1476
23 NOC4
4 Block ON
1
1477
23 NOC4
5 Block OFF
0
In the register of the NOC function is recorded start, trip or blocked “On” event process data.
In the table below is presented the structure of NOC function register content. This
information is available in 12 last recorded events for all provided instances separately.
Table 4.2.2.5-29. Register content.
Date & Time
Event
code
Fault
type
Trigger
current
Fault
current
Prefault
current
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
1280-
1477
Descr.
L1-G…
L1-L2-
L3
Start
average
current
Trip
-20 ms
averages
Start
-200 ms
averages
0 ms -
1800 s
1 - 8
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...