Instruction manual –AQ F210 Feeder Protection IED
64 (292
)
Table 4.2.1.3-23 Reset time characteristics setting parameters.
Release Time
delay
0.000…150.000 s
0.005 s
0.06 s
Resetting time. Time allowed in between
of pick-ups if the pick-up has not lead into
trip operation. During this time the start
signal is held on for the timers if delayed
pick-up release is active.
Delayed Pick-up
release
No
Yes
-
Yes
Resetting characteristics selection either
time delayed or instant after pick-up
element is released. If activated the start
signal is reset after set release time delay.
Time calc reset
after release time
No
Yes
-
Yes
Operating timer resetting characteristics
selection. When active the operating time
counter is reset after set release time if
pick-up element is not activated during this
time. When disabled the operating time
counter is reset directly after the pick-up
element reset.
Continue time
calculation during
release time
No
Yes
-
No
Time calculation characteristics selection.
If activated the operating time counter is
continuing until set release time even the
pick-up element is reset.
In following figures are presented the behavior of the stage in different release time
configurations.
Figure 4.2.1.3-18. No delayed pick-up release.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...