23

ADVANCED SETUP

10.5 

Flowmeter

Select
one item

Fig. 44 

 

Flowmeter out of range

Rate alarm

Set the installed flowmeter and the relevant data. Tab. A contains the values that will be automatically 
set by selecting the flowmeter code.
Nevertheless these data can be modified.

> Type

: indicate the type of installed flowmeter (Tab. A).

>  Min. flowrate alarm

>  Max. flowrate alarm

The rate alarms (minimum or maximum) activate when, during the treatment, the flowmeter rate does 
not respect the set limits.

For the procedure to be followed in case of alarms, please refer to Par. 14.1 Operation 
errors.

> Constant

: indicate the constant of the installed flowmeter.

orion fLowmeters

TYPE

METRIC - METR. l/100 m

UNITS OF MEASUREMENT

US

UNIT OF MEASUREMENT

The default values can be modified.

Constant

(pls/l)

Min. rate

(l/min)

Max. rate

(l/min)

Constant

(pls/gal)

GPM min. 

flowrate

GPM max. 

rate

4621xA0xxxx

6000

0.5

10.0

22710

0.13

2.60

4621xA1xxxx

3000

1.0

20.0

11355

0.30

5.00

4621xA2xxxx

2000

2.5

50.0

4542

0.60

13.00

4621xA3xxxx

600

5.0

100.0

2271

1.35

26.00

462xxA4xxxx

300

10.0

200.0

1135

2.60

53.00

4622xA5xxxx

150

20.0

400.0

568

5.00

106.00

4622xA6xxxx

100

30.0

600.0

378

8.00

158.00

Other...

625

10.0

100.0

156

2.60

53.00

Tab. A

10.6 

Pressure sensor

The pressure sensor has a different use according to the situations.

• Enabled flowmeter:

 displays the job pressure when the machine works within the flowmeter limits.

When the flowmeter operates outside the limits the measured pressure is used to calculate the spray rate.

• Disabled flowmeter:

 the pressure sensor is always used to calculate the application rate.

Select
one item

Fig. 45 

Set the type of installed pressure sensor and the relevant full scale.

> Type

: indicate the type of installed sensor (available models indicated in the table).

>  Maximum pressure

Indicate the full scale of the pressure sensor installed on the system.

When the option 

Disabled 

is activated, the item 

Maximum pressure

 is no longer 

displayed (Fig. 45).

The table below indicates the values that are automatically set selecting the sensor code:

arag pressure sensor

TYPE

Max. pressure

The default values can be 
modified.

bar

PSI

ARAG 466113.200

20.0

290

ARAG 466113.500

50.0

725

Other...

50.0

725

10.7 

Delivery cal. sensor

Fig. 46 

Set the type of sensor to be used to calculate the rate:

> Flowmeter

 Pressure

 Either

Within the working limits the computer uses the flowmeter, otherwise it uses the pressure sensor 
(ONLY if properly configured).

Par.9.3

Quick reset of
change

Menu item scrolling or
Data increase/decrease

Confirms access to menu
or data change

Quits the menu or
data changes

Содержание BRAVO 300S

Страница 1: ...300S Bravo series computer MULTI ROW SPRAYER DIRECT CONNECTION 46731XXX RCU 46733XXX Software rel 3 1x INSTALLATION use and maintenance...

Страница 2: ...al is an integral part of the equipment to which it refers and must accompany the equipment in case of sale or change of ownership Keep it for any future reference ARAG reserves the right to modify pr...

Страница 3: ...ctor connection FOR VERSIONS WITH DIRECT CONNECTION ONLY 14 8 2 Remote control unit RCU connection 14 8 3 Control unit valve connection 14 8 4 Hydraulic valves connection 15 8 5 Connection of sensors...

Страница 4: ...1 41 12 5 F4 Tank PAGE 1 42 12 6 F4 User setting PAGE 2 42 13 Use 43 13 1 Controls on computer 43 13 2 Control selection or modification keys 44 13 3 Operating switches for control unit valves 44 13 4...

Страница 5: ...The descriptions of the assembly phases refer to a general computer so specific models will not be mentioned unless a certain installation procedure concerns exclusively one computer type Responsibili...

Страница 6: ...standard Electromagnetic compatibility Forestry and farming machines harmonized with 2004 108 EC Directive 4 Precautions Do not aim water jets at the equipment Do not use solvents or fuel to clean th...

Страница 7: ...flowmeter Pump Protector RPM sensor X Level sensor 1 5 Section valves DIRECT CONNECTION ASSEMBLY DIAGRAM FOR MULTI ROW SPRAYER WITH DIAPHRAGM PUMP SYSTEM WITH DRAIN VALVE Fig 4 Legend A Monitor B Batt...

Страница 8: ...n valves RCU ASSEMBLY DIAGRAM FOR MULTI ROW SPRAYER WITH DIAPHRAGM PUMP SYSTEM WITH MAIN VALVE Fig 6 Legend A Monitor B Battery D Filling pump E Hydraulic unit F Flowmeter G Main valve L Level sensor...

Страница 9: ...c unit F Flowmeter G Drain valve L Level sensor M Pressure sensor P Control valve R Foam marker S Speed sensor T Filling flowmeter Pump Protector U RCU X RPM sensor 1 5 Section valves RCU ASSEMBLY DIA...

Страница 10: ...his view Control unit RCU secure the control unit on the back of the machine close to the control unit and the hydraulic unit Consider all necessary connections of the computer the cable length and m...

Страница 11: ...ckets supplied and fitted to the unit positioning it as shown in the manual provided with the assembly MAKE SURE TO FOLLOW ALL THE SAFETY INSTRUCTIONS GIVEN IN THE CONTROL UNIT S MANUAL 6 6 Hydraulic...

Страница 12: ...cables to protect against water infiltrations the cable branches must ALWAYS be face downwards see figures below DIRECT CONNECTION Fig 14 Fig 15 SYSTEM WITH RCU Fig 16 Fig 17 Fitting the cables to th...

Страница 13: ...y by the farming machine battery 12 Vdc ALWAYS switch on the computer through the monitor and then remember to switch it off using the specific key on the control panel If BRAVO 300S remains on for a...

Страница 14: ...2 each one of them shall be connected to the corresponding socket on the remote control unit If they prove hard to insert do not force them but check the shown position 8 3 Control unit valve connecti...

Страница 15: ...ion Fig 24 Bravo 300S can control up to 9 hydraulic functions through double acting valves Fix the connectors to the relevant valves according to the initials indicated in your assembly general diagra...

Страница 16: ...ndary connection T shall be used only if connection X is already occupied by another sensor Do not use the secondary input T if no sensor is connected to the X input otherwise the computer will not be...

Страница 17: ...t it correctly the card cut edge A must be face downward push the card until it engages into place and close the slot with the cover Removal Press and immediately release the card into the slot and sl...

Страница 18: ...ased Switching on to activate the advanced setup Fig 31 Contemporaneously press the key sequence until switching on the Bravo Release key ESC keeping pressed the arrow keys until the display shows the...

Страница 19: ...Exit without confirming the change press ESC ACCESS TO A SUBMENU Fig 35 In case of a submenu BRAVO 300S displays three dots 2b Fig 33 3b Press the arrow keys in succession to move across the menu ite...

Страница 20: ...rrow keys pressed until the menu is displayed For correct use of keys while programming refer to Par 9 3 ADVANCED SETUP MENU STRUCTURE Par 10 1 Par 10 2 Par 10 3 Par 10 4 Par 10 8 Par 10 5 Par 10 6 Pa...

Страница 21: ...Unit of measurement Fig 40 Set the units of measurement used for Bravo 300S Metric l h km h bar US GPA mil h PSI Metr L 100 m 10 3 Section valves number Fig 41 Set the number of installed section val...

Страница 22: ...de especially if the section automatic closing is active when the main control valve is closed No P mode Yes M mode It is compulsory to set the M mode option Yes when no main valve None is present in...

Страница 23: ...0 53 00 Tab A 10 6 Pressure sensor The pressure sensor has a different use according to the situations Enabled flowmeter displays the job pressure when the machine works within the flowmeter limits Wh...

Страница 24: ...ta in real time Capacity indicate the tank capacity Minimum level alarm indicate the range value Type indicate the filling flowmeter installed and the relevant data Tab B contains the values that will...

Страница 25: ...l menu activate the Level sensor mode Fig 54 and select the Calibration item Bravo 300S requests to enter the tank capacity Fig 56 enter the value 7 Immediately afterwards the computer passes to the c...

Страница 26: ...i row sprayer is used the recovered liquid count can be enabled during treatment The information will be available in the job data Par 12 2 F2 Current job data PAGE 1 10 10 Rev counter Select one item...

Страница 27: ...er Orion 462 or Other Rev counter pls turn Pump Protector Enabled Par 10 7 Par 10 5 Enable flowmeter The setting for the rate calculation requires the flowmeter which is disabled though Delivery cal s...

Страница 28: ...USER PROGRAMMING MENU STRUCTURE DEF Job 01 Job 02 Job 03 Target rate 60 l ha 90 l ha 120 l ha Row width 1 00 m 2 00 m 3 00 m Boom type A B C Fig 68 The minimum and maximum values relevant to the data...

Страница 29: ...distance traveled by the wheel with the speed sensor The longer the distance traveled the more accurate the wheel constant calculation Select the Wheel constant 1 2 or 3 and enter the calculated value...

Страница 30: ...te value for the selected treatment Bravo 300S carries out the treatment by keeping the set rate If the Variable option is set BRAVO 300S varies the output according to the data sent by the Skipper sa...

Страница 31: ...e l min Pressure bar Rate GPM Pressure PSI ATR White 0 21 3 00 0 050 40 ATR Lilac 0 28 3 00 0 070 40 ATR Brown 0 38 3 00 0 100 40 ATR Yellow 0 55 3 00 0 150 40 ATR Orange 0 77 3 00 0 200 40 ATR Red 1...

Страница 32: ...ayed fluid factor if at the end of the spraying the tank still contains fluid reduce the factor if the fluid finishes before the output has ended increase the factor Fig 86 Set the density factor of t...

Страница 33: ...d out at the frequency set in the Data logger menu Any time you select a job a new LOG file will be saved and its name Fig 91 will bear a progressive number according to the number of savings i e 0000...

Страница 34: ...he computer detects frequency and current sent by each sensor on the system Besides item T Filling flowm the display can show T Rev counter or T Pump Protector according to the connected sensor Par 8...

Страница 35: ...lable ONLY F Lock A Release B Lock b Neutral position G Inclination A Left B Right c Neutral position H Height A Lower B Lift a Neutral position I Functions A Opening B Closing 1 2 3 4 5 6 Neutral pos...

Страница 36: ...BIN is displayed at the end of the configuration Press ESC SD card not found Configuration alarm memory card not inserted Save to SD card Select to save Fig 100 Allows saving the Bravo 300S configura...

Страница 37: ...ig 103 TOTALIZER RECORD FILE File name structure Reference job number 01 19 Progressive number Fig 104 SAVING THE TOTALIZER ON SD CARD Select the item Save to SD card Fig 101 and press OK In the examp...

Страница 38: ...rent ways to access the functions of page 1 A use the arrow keys and press the relevant function key B press the relevant function key twice C keep the relevant key pressed for 3 seconds PAGE 2 Fig 10...

Страница 39: ...oncerning the job that has just been ended and saves them on the SD card in a new file If for example we have selected the Job No 01 and we want to change treatment by selecting Job No 03 the computer...

Страница 40: ...OUNTING ENABLED Master ON Master ON Rate ON Master OFF SAVING THE DATA ON SD CARD Select the item Save to SD card and press OK The current job report will be saved in the file indicated on the display...

Страница 41: ...luid to be poured in the tank in order to complete spraying the set area In the screen shown in Fig 112 press OK BRAVO 300S will display the fluid filled in the tank Estimated quantity need BRAVO 300S...

Страница 42: ...need Enter area to be sprayed The display will show the quantity of fluid to be poured in the tank in order to complete spraying the set area Fig 116 Tank level Level sensor mode Par 10 9 3 Level BRA...

Страница 43: ...fy parameters 3 Foam marker control keys 4 Operating switches for control unit valves BRAVO 300S WITH CONTROL UNIT RCU Fig 119 Legend 1 Function keys Chap 12 Job functions 2 Keys to select data or mod...

Страница 44: ...section movement closing 13 5 Display Fig 120 1 Preset rate Automatic mode Manual mode 2 Preset row width 3 Spraying status 4 Clock 5 Detected output 6 Output variation percentage 7 Speed 8 Pressure...

Страница 45: ...lves Par 13 4 Operating switches for hydraulic valves Par 13 5 Display 13 7 2 Manual operation Fig 122 Rate manual regulation shall be carried out with the suitable switch 1 Enable the manual operatio...

Страница 46: ...of the moving part 10 10 MAN AUTO Increase rotation speed RPM does not reach the minimum value Increase the rotation speed of the moving part 10 5 MAN AUTO Flowmeter out of range Rate out of the limi...

Страница 47: ...eck spray rate setup Par 11 2 Check the coverage setup and the row width Par 10 4 11 2 System not adequately sized to provide required rate Check maximum pressure valve setting Make sure control valve...

Страница 48: ...ata necessary to determine the instantaneous pressure 1 2200 US PSI Delivery cal sensor Sensor used to calculate the output Values that can be set Flowmeter Pressure Either Tank level Mode Values that...

Страница 49: ...type ATR Par 11 4 Booms setup Working limits Nozzles wear check Disab 50 Min spraying speed Disab 999 9 Metric L 100 m km h US MPH Regulation lock type Groups the options Disabled Min regulation speed...

Страница 50: ...ations carried out by unauthorised personnel incorrect installation and regulation damage or malfunction caused by the lack of ordinary maintenance such as cleaning of filters nozzles etc anything tha...

Страница 51: ...ravo 300S con unit decentrata Bravo 300S RCU serie 46732xxx versioni diserbo e sequenziale 46733xxx versioni multifilare 46737xxx versioni per Selejet risponde ai requisiti di conformit contemplati ne...

Страница 52: ...ia Palladio 5 A Tel 39 0522 622011 Fax 39 0522 628944 www aragnet com info aragnet com Only use genuine ARAG accessories or spare parts to make sure manufacturer guaranteed safety conditions are maint...

Отзывы: