– 78 –
3*15 Select either Steady or Pulsing for each bell circuit output
3*60 Select Timeout for Bell 2
3. Enter #93 Zone Progrmming mode to assign zones to bell outputs and/or
aux. relay.
4. Exit program mode by pressing *99.
The bell outputs will not respond if zones are not assigned to them. For fire
alarms, the system will display "FIRE ALARM SILENCED." This message will
also be displayed if the bell output is not supervised.
Wiring
By default, Bell 1 is set to operate as an unsupervised burglary bell output. You
may use any UL listed, non-polarized burglary indicating device rated for 10 -14
VDC operation on this output. Note that a local burglary grade A listing requires
that a bell in a tamper protected housing be used (such as the Ademco AB12)
and that bell wiring be run in conduit.
By default, Bell 2 is set to operate as a supervised fire bell output. Note that the
panel supervises this wiring for open, short and earth ground faults. You may
use any UL listed, polarized fire indicating device rated for 10 -14 VDC operation
on this output. Observe polarity when wiring polarized devices.
Compatible Alarm Indicating Devices
Compatible devices are listed below. The diagram shows how to make
connections to these outputs.
Model
Description
System Sensor PA400B
(beige)/ PA400R (red)
Indoor piezo sounder (red or beige), rated at 90
dB @ 10 feet.
System Sensor MA-12/24
Horn
System Sensor SS-12
Strobe
System Sensor SS1215 ADA
Strobe
System Sensor SS121575 ADA
Strobe
System Sensor MASS1215 ADA
Horn/Strobe
System Sensor MASS121575
ADA
Horn/Strobe
System Sensor MA/SS-12
Horn/Strobe
Wheelock LS1-12-VFR
Strobe
Wheelock MS1-12-VFR
Strobe
Wheelock MT-12-LS-VFR
Horn/Strobe
Wheelock MT4-12-LS-VFR
Horn/Strobe
Wheelock MT-12-MS-VFR
Horn/Strobe
Wheelock MT4-12-MS-VFR
Horn/Strobe
Gentex GXS-2-15
Strobe
Gentex GXS-2-1575
Strobe
Gentex SHG-12-15
Horn/Strobe
Gentex SHG-12-1575
Horn/Strobe
Faraday 5336L-U-14-12-DC
Horn/Strobe
Faraday 5337L-U-14-12-DC
Horn/Strobe
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...