– 178 –
When this test is first activated, the system will display:
USE BELL DING?
0 = NO 1 = YES
Enter (Y) to have the fire bells associated with each
point sound for 3 seconds when a point is faulted.
Enter (N) if only keypad sounders are desired. The
next prompt will be displayed.
AUTO-TEST DET?
0 = NO 1 = YE S
Enter (Y) to have the system automatically test all
polling loop points with a fire response type 9 or 16.
Other fire zones will have to be tested manually.
Enter (N) to test every point manually. The next
prompt will be displayed.
For true detector sensitivity tests, and for compliance with fire codes, you
must enter "0" (NO) to this question.
LOG RESULTS?
0 = NO 1 = YES
Enter (Y) to have the system log each point as it is
tested. A list of untested points will also be logged.
Enter (N) if you do not want the system to keep track
of the results. The next prompt will only be
displayed if Contact ID report format has been
selected.
C.S. TRANSMIT?
0 = NO 1 = YES
Enter (Y) to have the results of the test sent to the
central station. This report will consist of a list of
points that have been tested followed by a list of
points that have not been tested. Enter (0) if you do
not want to report the results. A "Walk Test Start"
and "Walk Test End" report will be sent in either
case (if programmed).
When the test mode is activated, the system will sound fire bells (or any bell
having a non-zero response type in field 3*10) for 3 seconds. The system will
also send a "Start of Walk Test" message to the central station, and will
light all keypad indicators and display window segments to verify that they
are working properly. The keypads will then display “Fire Walk Test in
Progress” and will sound a single beep every 15 seconds while this test is
active.
The system will build a list of all the fire zones (response types 9, 16, 17, 18)
that need to be tested. These points will be scrolled on the display. For each
point, the keypad will display "UNTST XXX," where XXX is the point
number followed by an alpha descriptor for the point.
If the AUTO-TEST option has been selected, the control panel will attempt
to automatically test all of the polling loop points that have a zone response
type of 9 or 16. For points that must be manually tested, fault and reset
each fire alarm sensor in turn. Each action should cause keypads to beep
and fire bells to ding. The keypads will display the zone number and the
associated alpha descriptor while the zone remains faulted. The system
automatically issues a smoke detector power reset about 10 seconds after it
finds a fault on one of these zones, to allow faulted detectors to be reset.
To end the test, enter any security code and press OFF. An "End of Walk
Test" message will be sent to the central station (if programmed). Note that
the test will automatically end if no faults are detected within a 30 minute
time period.
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...