115 –
RELAY PROG?
0=No 1=Yes
For defining output relay functions. This prompt is
fully explained in the 4204 RELAY MODULE section.
RLY VOICE DESCR?
0=No 1=Yes
For entering voice descriptors for relays to be used
with the 4285 VIP Module This prompt is fully
explained in the RELAY OUTPUTS section.
CUSTOM INDEX ?
0=No 1=Yes
For creating custom word substitutes for VIP Module
annunciation. This prompt is fully explained in the
4285 VIP MODULE section.
Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing
0 will display the next choice in sequence. Refer to the
ZONE PROGRAMMING
section for instructions on how to program zone characteristics, the
DEVICE
PROGRAMMING section for instructions on how to program addressable
devices, and the
ALPHA PROGRAMMING section for programming alpha
descriptors.
The following is a list of commands used while in the menu mode.
#93 Menu Mode Key Commands
#93
Enters Menu mode
[
✴
]
Serves as ENTER key. Press to have keypad accept entry.
[#]
Backs up to previous screen.
0
Press to answer NO
1
Press to answer YES
00
Escapes from menu mode, back into data field programming
mode, if entered at the first prompt of each main menu option.
Zone Programming
Enter Programming mode [Installer Code] + 8 0 0 0. The following fields should
be programmed before beginning:
2*00: Number of Partitions;
1*32: RF Receiver Type.
Also, before programming wireless zones, the RF receiver must be enabled in
Device Programming Mode (later in Device Programming section).
Then press #93 to display "ZONE PROG?".
ZONE PROG?
1=Yes 0=No
Press 1 to enter ZONE PROGRAMMING mode. The
following screens will appear. Press
✴
to display
the next screen. Press # to display a previous
screen.
ENTER ZN NO.
00=QUIT 020
Enter the 3-digit zone number to be programmed.
Press
✴
to accept entry.
020 ZT P RC B In:L
00 1 00 1 RF:N
A summary screen for that zone will appear.
ZT=Zone Type, P=Partition, RC=Report Code, B =
Bell/Aux Relay assignment for zone, In:=the input
type of device, and L=the device's loop number to
which the sensor is connected (some devices can
support more than one zone by means of individual
loops (ex. 5801, 5803, 5816, 5817, etc.)
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...