– 9 –
Do not
assign Partition 1 as the common lobby. All fire zones should be
assigned to this partition to ensure that all fire test modes operate correctly.
How User Access Codes Affect the Common Lobby
Codes with "Global" Arming
If a code is given "global arming" when it is defined (see Section 27:
USER
ACCESS CODES
), the keypad will ask a "Arm all?" or "Disarm all?" whenever
the user tries to arm or disarm the partitions he has access to from an alpha
keypad. This allows the user to pick and choose the partitions to be armed or
disarmed, and so eliminates the "automatic" operation of the lobby. Keep in
mind, however, that if attempting to arm all, and another "affecting" partition is
disarmed, the user will not be able to arm the lobby, and the message "UNABLE
TO ARM LOBBY PARTITION" will be displayed.
Codes with "Non-Global" Arming
If arming with a non-global code, the lobby partition operation will be automatic,
as described by fields 1*18 and 1*19.
Other Methods of Arming/Disarming
When arming or disarming a partition that affects and/or arms the common lobby
in one of the following manners, lobby logic remains active:
•
Quick-Arm
•
Keyswitch
•
Wireless Button
•
Wireless Keypad
Arming/Disarming Remotely
If arming or disarming remotely (through VLINK downloading software), the lobby
will not automatically follow another partition that is programmed to arm or disarm
the lobby. The lobby must be armed separately, after arming all affecting
partitions first.
Auto-Arming/Disarming
If scheduling is used to automatically arm and/or disarm partitions, the Lobby
partition will not automatically follow another partition that is programmed to arm
or disarm the lobby. The lobby must be included as a partition to be
armed/disarmed.
If using auto-arming, make sure that the Auto-arm Delay and Auto-arm
Warning periods (fields 2*05 and 2*06) combined are longer than that of any
other partition that affects the lobby. This will cause the lobby to arm last.
Master Keypad Setup and Operation
Although this system has eight actual partitions, it provides an extra partition
strictly for the purpose of assigning keypads as "Master" keypads for the system.
Any keypad assigned to Partition 9 in #93 Device Programming mode will make
that keypad a "Master" keypad. A Master keypad reflects the status of the entire
system (Partitions 1-8) on its display at one time. This is useful because it
eliminates the need for a security officer in a building to have to "log-on" to
various partitions from one partition's keypad to find out where an alarm has
occurred.
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...