– 153 –
Ademco Contact ID Reporting takes the following format:
CCCC QEEE GG ZZZ
where: CCCC =
Customer (subscriber) ID
Q =
Event qualifier, where:
E = new event , and R = restore
EEE = Event code (3 hexadecimal digits)
GG = Partition Number (system messages show “00”)
ZZZ = Zone/contact ID number reporting the alarm, or user
number for open/close reports. System status
messages (AC Loss, Walk Test, etc.) contain zeroes in
the ZZZ location.
Ademco High Speed Reporting events by channel:
Channels 1 through 8 could have one of the following conditions:
1 = NEW EVENT
2 = OPENING (Status Channel Always = 2)*
3 = RESTORE
4 = CLOSING (Status Channel Always = 4)*
5 = NORMAL, NO EVENT TO REPORT
6 = PREVIOUSLY REPORTED, NOT YET RESTORED
* NOTE: Channel 1 will contain the user ID 1-9, A-F if Open/Close reporting
is enabled.
The status channel might have one of the following conditions:
1 = DURESS (For Duress Plus Channels 9-15 Only)
2 = OPENING
3 = BYPASS (For Channels 1-8 Only)
4 = CLOSING
5 = SUPERVISORY/TROUBLE (For Channels 1-8 Only)
6 = SYSTEM STATUS:
• AC LOSS in Channel 1
• LOW BATTERY in Channel 2
• TIME SET in Channel 3
• LOG CLEAR in Channel 3
• LOG 50% FULL in Channel 3
• LOG 90% FULL in Channel 3
• LOG OVERFLOW in Channel 3
• POWER ON RESET in Channel 4
• WALK TEST START, END in Channel 8
7 = NORMAL ALARM STATUS (Channels 1-8 Only)
9 = TEST REPORT
Explanation of Channels 9-15:
If there is a 1 in the status channel, and:
1 in the 1st location = Duress
1 in Channels 9-15 = Zone alarm on those channels
3 in Channels 9-15 = Restore on those channels
6 in Channels 9-15 = Previously reported alarm–not restored.
A typical high speed report may look as follows:
1234 5115 5555 7 (Acct #1234 with alarms on channels 2 and 3)
1234 5555 1555 1 (Acct #1234 with alarm on channel 12)
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...