– 72 –
Faulted zones must either be corrected or bypassed before the system will arm.
(ARMED)
(READY)
RED
GREEN
820
Ω
820
Ω
TAMPER
SWITCH
(N.C.)
LOCK
SWITCH (N.O.)
2000
OHMS
2000
OHMS
EOLR
TO ZONE 8 + (TERM 27)
TO ZONE 7 + (TERM 25)
TO ZONE 7/ZONE 8 – (TERM 26)
▲
▲
4146 KEYSWITCH
BROKEN LINES REPRESENT
INSTALLER WIRING CONNECTIONS
TO OUT 1 (J2 PIN 7)
TO OUT 5 (J2 PIN 6)
TO GND (J2 PIN 8)
Figure 17: Remote Keyswitch Wiring
UL
In commercial fire installations, mount the keyswitch next to a keypad. The
keypad will provide the UL required "Fire Bell Silenced" indication when the
keyswitch is used to silence a fire alarm.
With Alarms Present:
A momentary short across Zone 7 will silence alarm bell and keypad sounds, and
will disarm the system if it was armed. The keyswitch LEDs provide a memory of
alarm indication (see table below). A subsequent short across Zone 7 will clear
the alarm memory indication and reset 2-wire smoke and glass break detectors
(if used).
When field *15 is set to "9", the keyswitch operates as follows:
A momentary short across Zone 7 will silence alarm bell sounds (i.e. turn off Bell
1, Bell 2 and the aux relay if programmed for alarms) only if a fire alarm is
present. Outputs will re-sound automatically if a new fire alarm condition is
detected. Burglary alarms will not trigger the bell output until a User Code + OFF
is entered at the keypad. A momentary short has no effect if there are no fire
alarms present. This mode is intended to be used where it is desired to provide
the fire department with keyswitch silence capability without compromising the
burglary system's security.
LED indications are defined as follows:
GREEN
RED
MEANING
OFF
OFF
DISARMED & NOT READY
ON
OFF
DISARMED & READY
OFF
ON STEADY
ARMED AWAY
OFF
SLOW FLASH
ARMED STAY
OFF
RAPID FLASH
ALARM MEMORY
Open/close reporting for keyswitch is enabled in field *40, and the keyswitch
reports as user 0.
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...