– 106 –
1*22
CROSS ZONING PAIR ONE
| |
Enter the first pair of zones which must both be faulted within a five
minute period to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL Burglary Installations.
1*23
CROSS ZONING PAIR TWO
| |
Enter the second pair of zones which must both be faulted within a five
minute period to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL Burglary Installations.
1*24
CROSS ZONING PAIR THREE
| |
Enter the third pair of zones which must both be faulted within a five
minute period to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL Burglary Installations.
1*25
CROSS ZONING PAIR FOUR
| |
Enter the fourth pair of zones which must both be faulted within a five
minute period to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL Burglary Installations.
1*28
RF TX LOW BATTERY SOUND
[0]
Enter 0 if audible beep and display annunciation upon RF transmitter low
battery condition is desired only in disarmed state.
Enter 1 if audible beep and display is desired in both armed and
disarmed states.
Must be 1 for UL.
1*29
RF TX LOW BATTERY REPORT ENABLE
[0]
Enter 1 if a trouble message for RF transmitter low battery conditions is
to be sent to the central station.
Enter 0 if no report for transmitter low battery is desired. Note that a
trouble message will be sent for a transmitter supervision failure
independent of this selection.
Must be 1 for UL.
1*30
RF RCVR SUPERVISION CHECK-IN INTERVAL
[06]
Enter the check-in monitoring interval in 2-hour increments.
Enter 02-15 times 2 hours (4-30 hours).
Failure of a receiver to receive any RF signal within the time entered will
result in activation of the response type programmed for zone 990 for the
first receiver and zone 988 for the second receiver and their related
communication reports.
Enter 00 to disable receiver supervision.
Max. "6" (12 hr) for UL.
1*31
RF TRANSMITTER CHECK-IN INTERVAL
[12] |
Enter the check-in monitoring interval in 2-hour increments;
Enter 02-15 times 2 hours (4-30 hours).
Failure of an individual transmitter to send a supervision signal within the
time entered will result in a trouble response and related communication
report. Entry 00 disables transmitter supervision.
Max. "6" (12 hr) for UL.
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...