– 96 –
Type 05: Trouble by Day/Alarm by Night.
This zone type will give an instant alarm if faulted when
armed in the Away, Stay, Instant or Maximum (night)
modes. During the disarmed state (day), the system will
provide a latched trouble sounding from the keypad
(and a central station report, if desired). This zone type
is usually assigned to a zone which contains a foil-
protected door or window (such as in a store), or to a
zone covering a "sensitive" area such as a stock room,
drug supply room, etc. This zone type can also be used
on a sensor or contact in an area where immediate
notification of an entry is desired.
Type 06: 24-hour Silent Alarm.
This zone type sends a report to the Central Station but
provides no keypad display or sounding. This zone type
is usually assigned to a zone containing an Emergency
button.
Type 07: 24-hour Audible Alarm .
This zone type sends a report to the Central Station,
and provides an alarm sound at the keypad, and an
audible external alarm. This zone type is usually
assigned to a zone that has an Emergency button.
Type 08: 24-hour Auxiliary Alarm.
This zone type sends a report to Central Station and
provides an alarm sound at the keypad. (No bell output
is provided). This zone type is usually assigned to a
zone containing a button for use in personal
emergencies, or to a zone containing monitoring
devices such as water sensors, temperature sensors,
etc.
Type 09: Supervised Fire (Without Verification)
This zone type provides a fire alarm on short circuit and
a trouble condition on open circuit. The bell output must
be programmed to pulse when this zone type is shorted.
This zone type is always active and cannot be
bypassed.
Type 10 : Interior w/Delay
This zone type gives entry and exit delays (using the
programmed entry/exit time), if tripped when the panel
is armed in the Away mode. This zone type is also
active during Maximum mode, but no entry delay is
provided (alarms occur immediately if zone is tripped).
This zone type is automatically bypassed when the
panel is armed in the Stay or Instant modes. Delay
begins whenever sensors in this zone are violated,
regardless of whether or not an entry/exit delay zone
was tripped first.
NOTE FOR PANIC KEYS: Keypad panic zones share
the same zone response type for all 8 partitions, but
panics may be individually enabled for each partition.
Type 16: Fire With Verification
This zone type is used when smoke alarm verification is
desired on hardwire and polling loop zones containing
only 2-wire or 4-wire smoke detectors. An open will
initiate a trouble response and a short will initiate a fire
alarm response. Initial short detection causes 6-second
smoke detector power reset. Subsequent short
detection within 90 seconds of reset causes fire alarm.
Type 17: Fire Waterflow
An open on this zone causes a trouble response.
Shorts which remain present longer than the
programmed time delay (fields 3*16 & 3*18) cause a fire
alarm response. This zone can either be silenced by
Code + Off or when waterflow restores (programmed in
field 3*14).
Type 18: Fire Supervisory
This zone type is assigned to a zone having sensors
which monitor fire sprinkler systems (i.e., PIV switches,
etc.). An open on this zone causes a trouble. Shorts
can be programmed either for a trouble or an alarm
response based on the entry in data field 3*13.
Type 19: 24 Hour Trouble
An open or short on this zone type causes a trouble
response. No external alarm sounders are activated.
Type 20: Arm-Stay *
This is a special purpose zone type used with 5800
series wireless transmitters, and which will result in
arming the system in the STAY mode when the zone is
activated.
Type 21: Arm-Away *
This is a special purpose zone type used with 5800
series wireless transmitters, and which will result in
arming the system in the AWAY mode when the zone is
activated.
Type 22: Disarm*
This is a special purpose zone type used with 5800
series wireless transmitters, and which will result in
disarming the system when the zone is activated.
Type 23: No Alarm Response
This zone type can be used on a zone when an output
relay action is desired, but with no accompanying alarm
(ex. lobby door access).
* Note that these zone types are for use by 5800 series
devices
only!.
IMPORTANT! FAULT ANNUNCIATION
Polling loop and RF troubles (zones 988, 990 & 997)
will report as trouble conditions only, and as such,
should be assigned zone type 19 if annunciation is
desired. See SUPERVISION notes in POLLING
LOOP and WIRELESS EXPANSION sections for more
information.
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...