![ADEMCO VISTA-100 Скачать руководство пользователя страница 101](http://html1.mh-extra.com/html/ademco/vista-100/vista-100_installation-instructions-manual_2850251101.webp)
– 91 –
TOTAL CONTROL PANEL LOAD WORKSHEETS
To calculate the total current for the Aux. power 1, Aux power 2, bell 1 & bell 2 outputs and polling loop current,
multiply the each device's standby and/or alarm current by the number of units used.
1)
Enter devices used on
aux. power 1 output,
calculate standby and
alarm currents, then add
to get aux. power 1
current subtotal.
AUX. POWER 1 OUTPUT
Total Current
Device Model #
Device Current
X
# of Units
=
Standby
Alarm
Aux. Power 1 Output Subtotal
(terminals 10 & 11)
1.0A max
1.7A max
2)
Enter devices used on
aux. power 2 output,
calculate standby and
alarm currents, then add
to get aux. power 2
current subtotal.
AUX. POWER 2 OUTPUT
Total Current
Device Model #
Device Current
X
# of Units
=
Standby
Alarm
Aux. Power 2 Output Subtotal
(connector J4-pin 5)
400mA max
400mA max
3)
Enter devices connected
to bell 1 output, calculate
alarm currents, then add
to get bell 1 output
current subtotal.
BELL 1 OUTPUT
Total Current
Device Model #
Device Current
X
# of Units
=
Standby
Alarm
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
Bell 1 Output Subtotal (terminals 3 & 4) 1.7amp max
XXXXXX
4)
Enter devices connected
to bell 2 output, calculate
alarm currents, then add
to get bell 2 output
current subtotal.
BELL 2 OUTPUT
Total Current
Device Model #
Device Current
X
# of Units
=
Standby
Alarm
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
Bell 2 Output Subtotal (terminals 5 & 6) 1.7amp max
XXXXXX
5)
Enter the total polling
loop current using
values calculated in the
polling loop worksheet.
POLLING LOOP
Total Current
Standby
Alarm
(Enter worksheet total in both standby & alarm columns)
Polling Loop Subtotal
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...